475 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 0.88V (0.21%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.09V (0.26%)
Voltage at Load414.1 VLine Loss: 724.3 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A176.06 V (42.42%)238.9 V290.42 V (69.98%)144851.2 WDrop High
2.5 mm²24 A18 A105.64 V (25.45%)309.4 V174.25 V (41.99%)86910.8 WDrop High
4 mm²32 A25 A66.02 V (15.91%)349.0 V108.91 V (26.24%)54319.2 WDrop High
6 mm²41 A32 A44.02 V (10.61%)371.0 V72.61 V (17.5%)36212.8 WDrop High
10 mm²57 A44 A26.41 V (6.36%)388.6 V43.56 V (10.5%)21727.7 WDrop High
16 mm²76 A59 A16.51 V (3.98%)398.5 V27.23 V (6.56%)13579.8 WDrop High
25 mm²101 A78 A10.56 V (2.55%)404.4 V17.43 V (4.2%)8691.1 WDrop High
35 mm²125 A97 A7.55 V (1.82%)407.5 V12.45 V (3.0%)6207.9 WDrop High
50 mm²151 A118 A5.28 V (1.27%)409.7 V8.71 V (2.1%)4345.5 WDrop High
70 mm²192 A150 A3.77 V (0.91%)411.2 V6.22 V (1.5%)3104.0 WDrop High
95 mm²232 A181 A2.78 V (0.67%)412.2 V4.59 V (1.1%)2287.1 WDrop High
120 mm²269 A210 A2.2 V (0.53%)412.8 V3.63 V (0.87%)1810.6 WDrop High
150 mm²309 A241 A1.76 V (0.42%)413.2 V2.9 V (0.7%)1448.5 WDrop High
185 mm²353 A275 A1.43 V (0.34%)413.6 V2.35 V (0.57%)1174.5 WDrop High
240 mm²415 A324 A1.1 V (0.27%)413.9 V1.82 V (0.44%)905.3 WDrop High
300 mm²477 A372 A0.88 V (0.21%)414.1 V1.45 V (0.35%)724.3 W✓ OK (≤3%)
400 mm²570 A445 A0.66 V (0.16%)414.3 V1.09 V (0.26%)543.2 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 15m at 415V (voltage drop: 0.88V or 0.21%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.