475 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 1.17V (0.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.45V (0.35%)
Voltage at Load413.8 VLine Loss: 965.7 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A234.75 V (56.57%)180.2 V387.23 V (93.31%)193135.0 WDrop High
2.5 mm²24 A18 A140.85 V (33.94%)274.1 V232.34 V (55.98%)115881.0 WDrop High
4 mm²32 A25 A88.03 V (21.21%)327.0 V145.21 V (34.99%)72425.6 WDrop High
6 mm²41 A32 A58.69 V (14.14%)356.3 V96.81 V (23.33%)48283.8 WDrop High
10 mm²57 A44 A35.21 V (8.48%)379.8 V58.08 V (14.0%)28970.2 WDrop High
16 mm²76 A59 A22.01 V (5.3%)393.0 V36.3 V (8.75%)18106.4 WDrop High
25 mm²101 A78 A14.09 V (3.39%)400.9 V23.23 V (5.6%)11588.1 WDrop High
35 mm²125 A97 A10.06 V (2.42%)404.9 V16.6 V (4.0%)8277.2 WDrop High
50 mm²151 A118 A7.04 V (1.7%)408.0 V11.62 V (2.8%)5794.1 WDrop High
70 mm²192 A150 A5.03 V (1.21%)410.0 V8.3 V (2.0%)4138.6 WDrop High
95 mm²232 A181 A3.71 V (0.89%)411.3 V6.11 V (1.47%)3049.5 WDrop High
120 mm²269 A210 A2.93 V (0.71%)412.1 V4.84 V (1.17%)2414.2 WDrop High
150 mm²309 A241 A2.35 V (0.57%)412.7 V3.87 V (0.93%)1931.3 WDrop High
185 mm²353 A275 A1.9 V (0.46%)413.1 V3.14 V (0.76%)1566.0 WDrop High
240 mm²415 A324 A1.47 V (0.35%)413.5 V2.42 V (0.58%)1207.1 WDrop High
300 mm²477 A372 A1.17 V (0.28%)413.8 V1.94 V (0.47%)965.7 W✓ OK (≤3%)
400 mm²570 A445 A0.88 V (0.21%)414.1 V1.45 V (0.35%)724.3 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 20m at 415V (voltage drop: 1.17V or 0.28%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.