⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

475 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 13.21V (1.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 43.56V (6.31%)
Voltage at Load676.8 VLine Loss: 10863.9 W
Max Power & Breaker567.68 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7042.52 V (1020.65%)0.0 V11616.86 V (1683.6%)5794050.0 WDrop High
2.5 mm²24 A18 A4225.51 V (612.39%)0.0 V6970.12 V (1010.16%)3476430.0 WDrop High
4 mm²32 A25 A2640.94 V (382.75%)0.0 V4356.32 V (631.35%)2172768.8 WDrop High
6 mm²41 A32 A1760.63 V (255.16%)0.0 V2904.22 V (420.9%)1448512.5 WDrop High
10 mm²57 A44 A1056.38 V (153.1%)0.0 V1742.53 V (252.54%)869107.5 WDrop High
16 mm²76 A59 A660.24 V (95.69%)29.8 V1089.08 V (157.84%)543192.2 WDrop High
25 mm²101 A78 A422.55 V (61.24%)267.4 V697.01 V (101.02%)347643.0 WDrop High
35 mm²125 A97 A301.82 V (43.74%)388.2 V497.87 V (72.15%)248316.4 WDrop High
50 mm²151 A118 A211.28 V (30.62%)478.7 V348.51 V (50.51%)173821.5 WDrop High
70 mm²192 A150 A150.91 V (21.87%)539.1 V248.93 V (36.08%)124158.2 WDrop High
95 mm²232 A181 A111.2 V (16.12%)578.8 V183.42 V (26.58%)91485.0 WDrop High
120 mm²269 A210 A88.03 V (12.76%)602.0 V145.21 V (21.05%)72425.6 WDrop High
150 mm²309 A241 A70.43 V (10.21%)619.6 V116.17 V (16.84%)57940.5 WDrop High
185 mm²353 A275 A57.1 V (8.28%)632.9 V94.19 V (13.65%)46978.8 WDrop High
240 mm²415 A324 A44.02 V (6.38%)646.0 V72.61 V (10.52%)36212.8 WDrop High
300 mm²477 A372 A35.21 V (5.1%)654.8 V58.08 V (8.42%)28970.2 WDrop High
400 mm²570 A445 A26.41 V (3.83%)663.6 V43.56 V (6.31%)21727.7 W~ ≤5%

FAQ — 475 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 475A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 475A over 600m at 690V (voltage drop: 13.21V or 1.92%).

What is the power capacity of 475A at 690V?

At unity power factor, 475A at 690V supports 567.68 kW with a standard 500A circuit breaker.