⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

5 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 12.36V (2.98%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 12.23V (2.95%)
Voltage at Load402.6 VLine Loss: 107.0 W
Max Power & Breaker3.59 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A12.36 V (2.98%)402.6 V20.38 V (4.91%)107.0 W✓ OK (≤3%)
2.5 mm²24 A18 A7.41 V (1.79%)407.6 V12.23 V (2.95%)64.2 W✓ OK (≤3%)
4 mm²32 A25 A4.63 V (1.12%)410.4 V7.64 V (1.84%)40.1 W✓ OK (≤3%)
6 mm²41 A32 A3.09 V (0.74%)411.9 V5.1 V (1.23%)26.7 W✓ OK (≤3%)
10 mm²57 A44 A1.85 V (0.45%)413.1 V3.06 V (0.74%)16.0 W✓ OK (≤3%)
16 mm²76 A59 A1.16 V (0.28%)413.8 V1.91 V (0.46%)10.0 W✓ OK (≤3%)
25 mm²101 A78 A0.74 V (0.18%)414.3 V1.22 V (0.29%)6.4 W✓ OK (≤3%)
35 mm²125 A97 A0.53 V (0.13%)414.5 V0.87 V (0.21%)4.6 W✓ OK (≤3%)
50 mm²151 A118 A0.37 V (0.09%)414.6 V0.61 V (0.15%)3.2 W✓ OK (≤3%)
70 mm²192 A150 A0.26 V (0.06%)414.7 V0.44 V (0.11%)2.3 W✓ OK (≤3%)
95 mm²232 A181 A0.2 V (0.05%)414.8 V0.32 V (0.08%)1.7 W✓ OK (≤3%)
120 mm²269 A210 A0.15 V (0.04%)414.8 V0.25 V (0.06%)1.3 W✓ OK (≤3%)
150 mm²309 A241 A0.12 V (0.03%)414.9 V0.2 V (0.05%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.1 V (0.02%)414.9 V0.17 V (0.04%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)414.9 V0.13 V (0.03%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.01%)414.9 V0.1 V (0.02%)0.5 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)415.0 V0.08 V (0.02%)0.4 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 5A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 5A over 100m at 415V (voltage drop: 12.36V or 2.98%).

What is the power capacity of 5A at 415V?

At unity power factor, 5A at 415V supports 3.59 kW with a standard 6A circuit breaker.