5 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 18.53V (2.69%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 19.11V (2.77%)
Voltage at Load671.5 VLine Loss: 160.5 W
Max Power & Breaker5.98 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (4.48%)659.1 V50.95 V (7.38%)267.5 W~ ≤5%
2.5 mm²24 A18 A18.53 V (2.69%)671.5 V30.57 V (4.43%)160.5 W✓ OK (≤3%)
4 mm²32 A25 A11.58 V (1.68%)678.4 V19.11 V (2.77%)100.3 W✓ OK (≤3%)
6 mm²41 A32 A7.72 V (1.12%)682.3 V12.74 V (1.85%)66.9 W✓ OK (≤3%)
10 mm²57 A44 A4.63 V (0.67%)685.4 V7.64 V (1.11%)40.1 W✓ OK (≤3%)
16 mm²76 A59 A2.9 V (0.42%)687.1 V4.78 V (0.69%)25.1 W✓ OK (≤3%)
25 mm²101 A78 A1.85 V (0.27%)688.1 V3.06 V (0.44%)16.1 W✓ OK (≤3%)
35 mm²125 A97 A1.32 V (0.19%)688.7 V2.18 V (0.32%)11.5 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.13%)689.1 V1.53 V (0.22%)8.0 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.1%)689.3 V1.09 V (0.16%)5.7 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.07%)689.5 V0.8 V (0.12%)4.2 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.06%)689.6 V0.64 V (0.09%)3.3 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.04%)689.7 V0.51 V (0.07%)2.7 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.04%)689.7 V0.41 V (0.06%)2.2 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.03%)689.8 V0.32 V (0.05%)1.7 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.02%)689.8 V0.25 V (0.04%)1.3 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.02%)689.9 V0.19 V (0.03%)1.0 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 5A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 5A over 250m at 690V (voltage drop: 18.53V or 2.69%).

What is the power capacity of 5A at 690V?

At unity power factor, 5A at 690V supports 5.98 kW with a standard 6A circuit breaker.