⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

5 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)1.5 mm²Drop: 0.71V (2.97%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 0.71V (2.94%)
Voltage at Load23.3 VLine Loss: 3.6 W
Max Power & Breaker0.12 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A0.71 V (2.97%)23.3 V1.18 V (4.9%)3.6 W✓ OK (≤3%)
2.5 mm²24 A18 A0.43 V (1.78%)23.6 V0.71 V (2.94%)2.1 W✓ OK (≤3%)
4 mm²32 A25 A0.27 V (1.11%)23.7 V0.44 V (1.84%)1.3 W✓ OK (≤3%)
6 mm²41 A32 A0.18 V (0.74%)23.8 V0.29 V (1.23%)0.9 W✓ OK (≤3%)
10 mm²57 A44 A0.11 V (0.45%)23.9 V0.18 V (0.74%)0.5 W✓ OK (≤3%)
16 mm²76 A59 A0.07 V (0.28%)23.9 V0.11 V (0.46%)0.3 W✓ OK (≤3%)
25 mm²101 A78 A0.04 V (0.18%)24.0 V0.07 V (0.29%)0.2 W✓ OK (≤3%)
35 mm²125 A97 A0.03 V (0.13%)24.0 V0.05 V (0.21%)0.2 W✓ OK (≤3%)
50 mm²151 A118 A0.02 V (0.09%)24.0 V0.04 V (0.15%)0.1 W✓ OK (≤3%)
70 mm²192 A150 A0.02 V (0.06%)24.0 V0.03 V (0.11%)0.1 W✓ OK (≤3%)
95 mm²232 A181 A0.01 V (0.05%)24.0 V0.02 V (0.08%)0.1 W✓ OK (≤3%)
120 mm²269 A210 A0.01 V (0.04%)24.0 V0.01 V (0.06%)0.0 W✓ OK (≤3%)
150 mm²309 A241 A0.01 V (0.03%)24.0 V0.01 V (0.05%)0.0 W✓ OK (≤3%)
185 mm²353 A275 A0.01 V (0.02%)24.0 V0.01 V (0.04%)0.0 W✓ OK (≤3%)
240 mm²415 A324 A0.0 V (0.02%)24.0 V0.01 V (0.03%)0.0 W✓ OK (≤3%)
300 mm²477 A372 A0.0 V (0.01%)24.0 V0.01 V (0.02%)0.0 W✓ OK (≤3%)
400 mm²570 A445 A0.0 V (0.01%)24.0 V0.0 V (0.02%)0.0 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 5 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 5A at 5 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 1.5 mm² copper cable for 5A over 5m at 24V (voltage drop: 0.71V or 2.97%).

What is the power capacity of 5A at 24V?

At unity power factor, 5A at 24V supports 0.12 kW with a standard 6A circuit breaker.