5 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 0.54V (2.23%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 0.59V (2.45%)
Voltage at Load23.5 VLine Loss: 2.7 W
Max Power & Breaker0.12 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1.43 V (5.94%)22.6 V2.35 V (9.81%)7.1 WDrop High
2.5 mm²24 A18 A0.86 V (3.57%)23.1 V1.41 V (5.88%)4.3 W~ ≤5%
4 mm²32 A25 A0.54 V (2.23%)23.5 V0.88 V (3.68%)2.7 W✓ OK (≤3%)
6 mm²41 A32 A0.36 V (1.49%)23.6 V0.59 V (2.45%)1.8 W✓ OK (≤3%)
10 mm²57 A44 A0.21 V (0.89%)23.8 V0.35 V (1.47%)1.1 W✓ OK (≤3%)
16 mm²76 A59 A0.13 V (0.56%)23.9 V0.22 V (0.92%)0.7 W✓ OK (≤3%)
25 mm²101 A78 A0.09 V (0.36%)23.9 V0.14 V (0.59%)0.4 W✓ OK (≤3%)
35 mm²125 A97 A0.06 V (0.25%)23.9 V0.1 V (0.42%)0.3 W✓ OK (≤3%)
50 mm²151 A118 A0.04 V (0.18%)24.0 V0.07 V (0.29%)0.2 W✓ OK (≤3%)
70 mm²192 A150 A0.03 V (0.13%)24.0 V0.05 V (0.21%)0.2 W✓ OK (≤3%)
95 mm²232 A181 A0.02 V (0.09%)24.0 V0.04 V (0.15%)0.1 W✓ OK (≤3%)
120 mm²269 A210 A0.02 V (0.07%)24.0 V0.03 V (0.12%)0.1 W✓ OK (≤3%)
150 mm²309 A241 A0.01 V (0.06%)24.0 V0.02 V (0.1%)0.1 W✓ OK (≤3%)
185 mm²353 A275 A0.01 V (0.05%)24.0 V0.02 V (0.08%)0.1 W✓ OK (≤3%)
240 mm²415 A324 A0.01 V (0.04%)24.0 V0.01 V (0.06%)0.0 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.03%)24.0 V0.01 V (0.05%)0.0 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.02%)24.0 V0.01 V (0.04%)0.0 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 5A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 5A over 10m at 24V (voltage drop: 0.54V or 2.23%).

What is the power capacity of 5A at 24V?

At unity power factor, 5A at 24V supports 0.12 kW with a standard 6A circuit breaker.