5 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 5 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 0.6V (2.5%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 0.71V (2.94%)
Voltage at Load23.4 VLine Loss: 3.0 W
Max Power & Breaker0.12 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9.99 V (41.61%)14.0 V16.47 V (68.64%)49.9 WDrop High
2.5 mm²24 A18 A5.99 V (24.97%)18.0 V9.88 V (41.18%)30.0 WDrop High
4 mm²32 A25 A3.75 V (15.6%)20.3 V6.18 V (25.74%)18.7 WDrop High
6 mm²41 A32 A2.5 V (10.4%)21.5 V4.12 V (17.16%)12.5 WDrop High
10 mm²57 A44 A1.5 V (6.24%)22.5 V2.47 V (10.3%)7.5 WDrop High
16 mm²76 A59 A0.94 V (3.9%)23.1 V1.54 V (6.43%)4.7 W~ ≤5%
25 mm²101 A78 A0.6 V (2.5%)23.4 V0.99 V (4.12%)3.0 W✓ OK (≤3%)
35 mm²125 A97 A0.43 V (1.78%)23.6 V0.71 V (2.94%)2.1 W✓ OK (≤3%)
50 mm²151 A118 A0.3 V (1.25%)23.7 V0.49 V (2.06%)1.5 W✓ OK (≤3%)
70 mm²192 A150 A0.21 V (0.89%)23.8 V0.35 V (1.47%)1.1 W✓ OK (≤3%)
95 mm²232 A181 A0.16 V (0.66%)23.8 V0.26 V (1.08%)0.8 W✓ OK (≤3%)
120 mm²269 A210 A0.12 V (0.52%)23.9 V0.21 V (0.86%)0.6 W✓ OK (≤3%)
150 mm²309 A241 A0.1 V (0.42%)23.9 V0.16 V (0.69%)0.5 W✓ OK (≤3%)
185 mm²353 A275 A0.08 V (0.34%)23.9 V0.13 V (0.56%)0.4 W✓ OK (≤3%)
240 mm²415 A324 A0.06 V (0.26%)23.9 V0.1 V (0.43%)0.3 W✓ OK (≤3%)
300 mm²477 A372 A0.05 V (0.21%)24.0 V0.08 V (0.34%)0.2 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.16%)24.0 V0.06 V (0.26%)0.2 W✓ OK (≤3%)

FAQ — 5 Amp Cable Size at 70 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 5A at 70 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 5A over 70m at 24V (voltage drop: 0.6V or 2.5%).

What is the power capacity of 5A at 24V?

At unity power factor, 5A at 24V supports 0.12 kW with a standard 6A circuit breaker.