50 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 0.93V (0.13%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 0.96V (0.14%)
Voltage at Load689.1 VLine Loss: 80.2 W
Max Power & Breaker59.76 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.18 V (0.9%)683.8 V10.19 V (1.48%)535.0 WDrop High
2.5 mm²24 A18 A3.71 V (0.54%)686.3 V6.11 V (0.89%)321.0 WDrop High
4 mm²32 A25 A2.32 V (0.34%)687.7 V3.82 V (0.55%)200.6 WDrop High
6 mm²41 A32 A1.54 V (0.22%)688.5 V2.55 V (0.37%)133.8 WDrop High
10 mm²57 A44 A0.93 V (0.13%)689.1 V1.53 V (0.22%)80.2 W✓ OK (≤3%)
16 mm²76 A59 A0.58 V (0.08%)689.4 V0.96 V (0.14%)50.2 W✓ OK (≤3%)
25 mm²101 A78 A0.37 V (0.05%)689.6 V0.61 V (0.09%)32.1 W✓ OK (≤3%)
35 mm²125 A97 A0.26 V (0.04%)689.7 V0.44 V (0.06%)22.9 W✓ OK (≤3%)
50 mm²151 A118 A0.19 V (0.03%)689.8 V0.31 V (0.04%)16.1 W✓ OK (≤3%)
70 mm²192 A150 A0.13 V (0.02%)689.9 V0.22 V (0.03%)11.5 W✓ OK (≤3%)
95 mm²232 A181 A0.1 V (0.01%)689.9 V0.16 V (0.02%)8.4 W✓ OK (≤3%)
120 mm²269 A210 A0.08 V (0.01%)689.9 V0.13 V (0.02%)6.7 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.01%)689.9 V0.1 V (0.01%)5.3 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)689.9 V0.08 V (0.01%)4.3 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.01%)690.0 V0.06 V (0.01%)3.3 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.0%)690.0 V0.05 V (0.01%)2.7 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.0%)690.0 V0.04 V (0.01%)2.0 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 50A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 50A over 5m at 690V (voltage drop: 0.93V or 0.13%).

What is the power capacity of 50A at 690V?

At unity power factor, 50A at 690V supports 59.76 kW with a standard 50A circuit breaker.