50 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 50 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)10 mm²Drop: 7.41V (1.07%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 7.64V (1.11%)
Voltage at Load682.6 VLine Loss: 642.0 W
Max Power & Breaker59.76 kW50A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 50A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A49.42 V (7.16%)640.6 V81.52 V (11.81%)4280.0 WDrop High
2.5 mm²24 A18 A29.65 V (4.3%)660.3 V48.91 V (7.09%)2568.0 WDrop High
4 mm²32 A25 A18.53 V (2.69%)671.5 V30.57 V (4.43%)1605.0 WDrop High
6 mm²41 A32 A12.36 V (1.79%)677.6 V20.38 V (2.95%)1070.0 WDrop High
10 mm²57 A44 A7.41 V (1.07%)682.6 V12.23 V (1.77%)642.0 W✓ OK (≤3%)
16 mm²76 A59 A4.63 V (0.67%)685.4 V7.64 V (1.11%)401.2 W✓ OK (≤3%)
25 mm²101 A78 A2.97 V (0.43%)687.0 V4.89 V (0.71%)256.8 W✓ OK (≤3%)
35 mm²125 A97 A2.12 V (0.31%)687.9 V3.49 V (0.51%)183.4 W✓ OK (≤3%)
50 mm²151 A118 A1.48 V (0.21%)688.5 V2.45 V (0.35%)128.4 W✓ OK (≤3%)
70 mm²192 A150 A1.06 V (0.15%)688.9 V1.75 V (0.25%)91.7 W✓ OK (≤3%)
95 mm²232 A181 A0.78 V (0.11%)689.2 V1.29 V (0.19%)67.6 W✓ OK (≤3%)
120 mm²269 A210 A0.62 V (0.09%)689.4 V1.02 V (0.15%)53.5 W✓ OK (≤3%)
150 mm²309 A241 A0.49 V (0.07%)689.5 V0.82 V (0.12%)42.8 W✓ OK (≤3%)
185 mm²353 A275 A0.4 V (0.06%)689.6 V0.66 V (0.1%)34.7 W✓ OK (≤3%)
240 mm²415 A324 A0.31 V (0.04%)689.7 V0.51 V (0.07%)26.8 W✓ OK (≤3%)
300 mm²477 A372 A0.25 V (0.04%)689.8 V0.41 V (0.06%)21.4 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.03%)689.8 V0.31 V (0.04%)16.1 W✓ OK (≤3%)

FAQ — 50 Amp Cable Size at 40 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 50A at 40 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 10 mm² copper cable for 50A over 40m at 690V (voltage drop: 7.41V or 1.07%).

What is the power capacity of 50A at 690V?

At unity power factor, 50A at 690V supports 59.76 kW with a standard 50A circuit breaker.