125 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 125 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)35 mm²Drop: 6.62V (1.59%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 5.46V (1.32%)
Voltage at Load408.4 VLine Loss: 1433.0 W
Max Power & Breaker89.85 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A154.44 V (37.21%)260.6 V254.76 V (61.39%)33437.5 WDrop High
2.5 mm²24 A18 A92.66 V (22.33%)322.3 V152.85 V (36.83%)20062.5 WDrop High
4 mm²32 A25 A57.92 V (13.96%)357.1 V95.53 V (23.02%)12539.1 WDrop High
6 mm²41 A32 A38.61 V (9.3%)376.4 V63.69 V (15.35%)8359.4 WDrop High
10 mm²57 A44 A23.17 V (5.58%)391.8 V38.21 V (9.21%)5015.6 WDrop High
16 mm²76 A59 A14.48 V (3.49%)400.5 V23.88 V (5.76%)3134.8 WDrop High
25 mm²101 A78 A9.27 V (2.23%)405.7 V15.29 V (3.68%)2006.2 WDrop High
35 mm²125 A97 A6.62 V (1.59%)408.4 V10.92 V (2.63%)1433.0 W✓ OK (≤3%)
50 mm²151 A118 A4.63 V (1.12%)410.4 V7.64 V (1.84%)1003.1 W✓ OK (≤3%)
70 mm²192 A150 A3.31 V (0.8%)411.7 V5.46 V (1.32%)716.5 W✓ OK (≤3%)
95 mm²232 A181 A2.44 V (0.59%)412.6 V4.02 V (0.97%)528.0 W✓ OK (≤3%)
120 mm²269 A210 A1.93 V (0.47%)413.1 V3.18 V (0.77%)418.0 W✓ OK (≤3%)
150 mm²309 A241 A1.54 V (0.37%)413.5 V2.55 V (0.61%)334.4 W✓ OK (≤3%)
185 mm²353 A275 A1.25 V (0.3%)413.7 V2.07 V (0.5%)271.1 W✓ OK (≤3%)
240 mm²415 A324 A0.97 V (0.23%)414.0 V1.59 V (0.38%)209.0 W✓ OK (≤3%)
300 mm²477 A372 A0.77 V (0.19%)414.2 V1.27 V (0.31%)167.2 W✓ OK (≤3%)
400 mm²570 A445 A0.58 V (0.14%)414.4 V0.96 V (0.23%)125.4 W✓ OK (≤3%)

FAQ — 125 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 125A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 35 mm² copper cable for 125A over 50m at 415V (voltage drop: 6.62V or 1.59%).

What is the power capacity of 125A at 415V?

At unity power factor, 125A at 415V supports 89.85 kW with a standard 125A circuit breaker.