500 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 25 m (82.0 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 1.16V (0.28%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.91V (0.46%)
Voltage at Load413.8 VLine Loss: 1003.1 W
Max Power & Breaker359.4 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A308.88 V (74.43%)106.1 V509.51 V (122.77%)267500.0 WDrop High
2.5 mm²24 A18 A185.33 V (44.66%)229.7 V305.71 V (73.66%)160500.0 WDrop High
4 mm²32 A25 A115.83 V (27.91%)299.2 V191.07 V (46.04%)100312.5 WDrop High
6 mm²41 A32 A77.22 V (18.61%)337.8 V127.38 V (30.69%)66875.0 WDrop High
10 mm²57 A44 A46.33 V (11.16%)368.7 V76.43 V (18.42%)40125.0 WDrop High
16 mm²76 A59 A28.96 V (6.98%)386.0 V47.77 V (11.51%)25078.1 WDrop High
25 mm²101 A78 A18.53 V (4.47%)396.5 V30.57 V (7.37%)16050.0 WDrop High
35 mm²125 A97 A13.24 V (3.19%)401.8 V21.84 V (5.26%)11464.3 WDrop High
50 mm²151 A118 A9.27 V (2.23%)405.7 V15.29 V (3.68%)8025.0 WDrop High
70 mm²192 A150 A6.62 V (1.59%)408.4 V10.92 V (2.63%)5732.1 WDrop High
95 mm²232 A181 A4.88 V (1.18%)410.1 V8.04 V (1.94%)4223.7 WDrop High
120 mm²269 A210 A3.86 V (0.93%)411.1 V6.37 V (1.53%)3343.7 WDrop High
150 mm²309 A241 A3.09 V (0.74%)411.9 V5.1 V (1.23%)2675.0 WDrop High
185 mm²353 A275 A2.5 V (0.6%)412.5 V4.13 V (1.0%)2168.9 WDrop High
240 mm²415 A324 A1.93 V (0.47%)413.1 V3.18 V (0.77%)1671.9 WDrop High
300 mm²477 A372 A1.54 V (0.37%)413.5 V2.55 V (0.61%)1337.5 WDrop High
400 mm²570 A445 A1.16 V (0.28%)413.8 V1.91 V (0.46%)1003.1 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 25 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 500A at 25 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 25m at 415V (voltage drop: 1.16V or 0.28%).

What is the power capacity of 500A at 415V?

At unity power factor, 500A at 415V supports 359.4 kW with a standard 500A circuit breaker.