500 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.32V (0.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.82V (0.92%)
Voltage at Load412.7 VLine Loss: 2006.2 W
Max Power & Breaker359.4 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A617.76 V (148.86%)0.0 V1019.02 V (245.55%)535000.0 WDrop High
2.5 mm²24 A18 A370.66 V (89.32%)44.3 V611.41 V (147.33%)321000.0 WDrop High
4 mm²32 A25 A231.66 V (55.82%)183.3 V382.13 V (92.08%)200625.0 WDrop High
6 mm²41 A32 A154.44 V (37.21%)260.6 V254.76 V (61.39%)133750.0 WDrop High
10 mm²57 A44 A92.66 V (22.33%)322.3 V152.85 V (36.83%)80250.0 WDrop High
16 mm²76 A59 A57.92 V (13.96%)357.1 V95.53 V (23.02%)50156.2 WDrop High
25 mm²101 A78 A37.07 V (8.93%)377.9 V61.14 V (14.73%)32100.0 WDrop High
35 mm²125 A97 A26.48 V (6.38%)388.5 V43.67 V (10.52%)22928.6 WDrop High
50 mm²151 A118 A18.53 V (4.47%)396.5 V30.57 V (7.37%)16050.0 WDrop High
70 mm²192 A150 A13.24 V (3.19%)401.8 V21.84 V (5.26%)11464.3 WDrop High
95 mm²232 A181 A9.75 V (2.35%)405.2 V16.09 V (3.88%)8447.4 WDrop High
120 mm²269 A210 A7.72 V (1.86%)407.3 V12.74 V (3.07%)6687.5 WDrop High
150 mm²309 A241 A6.18 V (1.49%)408.8 V10.19 V (2.46%)5350.0 WDrop High
185 mm²353 A275 A5.01 V (1.21%)410.0 V8.26 V (1.99%)4337.8 WDrop High
240 mm²415 A324 A3.86 V (0.93%)411.1 V6.37 V (1.53%)3343.7 WDrop High
300 mm²477 A372 A3.09 V (0.74%)411.9 V5.1 V (1.23%)2675.0 WDrop High
400 mm²570 A445 A2.32 V (0.56%)412.7 V3.82 V (0.92%)2006.2 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 500A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 50m at 415V (voltage drop: 2.32V or 0.56%).

What is the power capacity of 500A at 415V?

At unity power factor, 500A at 415V supports 359.4 kW with a standard 500A circuit breaker.