⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 5.1V (1.27%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 8.41V (2.1%)
Voltage at Load394.9 VLine Loss: 4855.1 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1359.08 V (339.77%)0.0 V2241.85 V (560.46%)1294700.0 WDrop High
2.5 mm²24 A18 A815.45 V (203.86%)0.0 V1345.11 V (336.28%)776820.0 WDrop High
4 mm²32 A25 A509.66 V (127.41%)0.0 V840.69 V (210.17%)485512.5 WDrop High
6 mm²41 A32 A339.77 V (84.94%)60.2 V560.46 V (140.12%)323675.0 WDrop High
10 mm²57 A44 A203.86 V (50.97%)196.1 V336.28 V (84.07%)194205.0 WDrop High
16 mm²76 A59 A127.41 V (31.85%)272.6 V210.17 V (52.54%)121378.1 WDrop High
25 mm²101 A78 A81.54 V (20.39%)318.5 V134.51 V (33.63%)77682.0 WDrop High
35 mm²125 A97 A58.25 V (14.56%)341.8 V96.08 V (24.02%)55487.1 WDrop High
50 mm²151 A118 A40.77 V (10.19%)359.2 V67.26 V (16.81%)38841.0 WDrop High
70 mm²192 A150 A29.12 V (7.28%)370.9 V48.04 V (12.01%)27743.6 WDrop High
95 mm²232 A181 A21.46 V (5.36%)378.5 V35.4 V (8.85%)20442.6 WDrop High
120 mm²269 A210 A16.99 V (4.25%)383.0 V28.02 V (7.01%)16183.7 WDrop High
150 mm²309 A241 A13.59 V (3.4%)386.4 V22.42 V (5.6%)12947.0 WDrop High
185 mm²353 A275 A11.02 V (2.75%)389.0 V18.18 V (4.54%)10497.6 WDrop High
240 mm²415 A324 A8.49 V (2.12%)391.5 V14.01 V (3.5%)8091.9 WDrop High
300 mm²477 A372 A6.8 V (1.7%)393.2 V11.21 V (2.8%)6473.5 WDrop High
400 mm²570 A445 A5.1 V (1.27%)394.9 V8.41 V (2.1%)4855.1 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 100 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 100 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 100m at 400V (voltage drop: 5.1V or 1.27%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.