⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.64V (1.91%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 25.22V (6.31%)
Voltage at Load392.4 VLine Loss: 7282.7 W
Max Power & Breaker381.05 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4077.25 V (1019.31%)0.0 V6725.55 V (1681.39%)3884100.0 WDrop High
2.5 mm²24 A18 A2446.35 V (611.59%)0.0 V4035.33 V (1008.83%)2330460.0 WDrop High
4 mm²32 A25 A1528.97 V (382.24%)0.0 V2522.08 V (630.52%)1456537.5 WDrop High
6 mm²41 A32 A1019.31 V (254.83%)0.0 V1681.39 V (420.35%)971025.0 WDrop High
10 mm²57 A44 A611.59 V (152.9%)0.0 V1008.83 V (252.21%)582615.0 WDrop High
16 mm²76 A59 A382.24 V (95.56%)17.8 V630.52 V (157.63%)364134.4 WDrop High
25 mm²101 A78 A244.63 V (61.16%)155.4 V403.53 V (100.88%)233046.0 WDrop High
35 mm²125 A97 A174.74 V (43.68%)225.3 V288.24 V (72.06%)166461.4 WDrop High
50 mm²151 A118 A122.32 V (30.58%)277.7 V201.77 V (50.44%)116523.0 WDrop High
70 mm²192 A150 A87.37 V (21.84%)312.6 V144.12 V (36.03%)83230.7 WDrop High
95 mm²232 A181 A64.38 V (16.09%)335.6 V106.19 V (26.55%)61327.9 WDrop High
120 mm²269 A210 A50.97 V (12.74%)349.0 V84.07 V (21.02%)48551.2 WDrop High
150 mm²309 A241 A40.77 V (10.19%)359.2 V67.26 V (16.81%)38841.0 WDrop High
185 mm²353 A275 A33.06 V (8.26%)366.9 V54.53 V (13.63%)31492.7 WDrop High
240 mm²415 A324 A25.48 V (6.37%)374.5 V42.03 V (10.51%)24275.6 WDrop High
300 mm²477 A372 A20.39 V (5.1%)379.6 V33.63 V (8.41%)19420.5 WDrop High
400 mm²570 A445 A15.29 V (3.82%)384.7 V25.22 V (6.31%)14565.4 W~ ≤5%

FAQ — 550 Amp Cable Size at 300 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 550A at 300 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 300m at 400V (voltage drop: 7.64V or 1.91%).

What is the power capacity of 550A at 400V?

At unity power factor, 550A at 400V supports 381.05 kW with a standard 600A circuit breaker.