550 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)15× 400 mm²Drop: 1.37V (2.86%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 33.98V (70.78%)
Voltage at Load46.6 VLine Loss: 755.2 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5492.67 V (11443.06%)0.0 V9060.33 V (18875.69%)3020966.7 WDrop High
2.5 mm²24 A18 A3295.6 V (6865.83%)0.0 V5436.2 V (11325.42%)1812580.0 WDrop High
4 mm²32 A25 A2059.75 V (4291.15%)0.0 V3397.62 V (7078.39%)1132862.5 WDrop High
6 mm²41 A32 A1373.17 V (2860.76%)0.0 V2265.08 V (4718.92%)755241.7 WDrop High
10 mm²57 A44 A823.9 V (1716.46%)0.0 V1359.05 V (2831.35%)453145.0 WDrop High
16 mm²76 A59 A514.94 V (1072.79%)0.0 V849.41 V (1769.6%)283215.6 WDrop High
25 mm²101 A78 A329.56 V (686.58%)0.0 V543.62 V (1132.54%)181258.0 WDrop High
35 mm²125 A97 A235.4 V (490.42%)0.0 V388.3 V (808.96%)129470.0 WDrop High
50 mm²151 A118 A164.78 V (343.29%)0.0 V271.81 V (566.27%)90629.0 WDrop High
70 mm²192 A150 A117.7 V (245.21%)0.0 V194.15 V (404.48%)64735.0 WDrop High
95 mm²232 A181 A86.73 V (180.68%)0.0 V143.06 V (298.04%)47699.5 WDrop High
120 mm²269 A210 A68.66 V (143.04%)0.0 V113.25 V (235.95%)37762.1 WDrop High
150 mm²309 A241 A54.93 V (114.43%)0.0 V90.6 V (188.76%)30209.7 WDrop High
185 mm²353 A275 A44.54 V (92.78%)3.5 V73.46 V (153.05%)24494.3 WDrop High
240 mm²415 A324 A34.33 V (71.52%)13.7 V56.63 V (117.97%)18881.0 WDrop High
300 mm²477 A372 A27.46 V (57.22%)20.5 V45.3 V (94.38%)15104.8 WDrop High
400 mm²570 A445 A20.6 V (42.91%)27.4 V33.98 V (70.78%)11328.6 WDrop High

FAQ — 550 Amp Cable Size at 350 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 350 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 15× 400 mm² copper cable for 550A over 350m at 48V (voltage drop: 1.37V or 2.86%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.