550 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)25× 400 mm²Drop: 1.41V (2.94%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 58.24V (121.34%)
Voltage at Load46.6 VLine Loss: 776.8 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A9416.0 V (19616.67%)0.0 V15532.0 V (32358.33%)5178800.0 WDrop High
2.5 mm²24 A18 A5649.6 V (11770.0%)0.0 V9319.2 V (19415.0%)3107280.0 WDrop High
4 mm²32 A25 A3531.0 V (7356.25%)0.0 V5824.5 V (12134.38%)1942050.0 WDrop High
6 mm²41 A32 A2354.0 V (4904.17%)0.0 V3883.0 V (8089.58%)1294700.0 WDrop High
10 mm²57 A44 A1412.4 V (2942.5%)0.0 V2329.8 V (4853.75%)776820.0 WDrop High
16 mm²76 A59 A882.75 V (1839.06%)0.0 V1456.12 V (3033.59%)485512.5 WDrop High
25 mm²101 A78 A564.96 V (1177.0%)0.0 V931.92 V (1941.5%)310728.0 WDrop High
35 mm²125 A97 A403.54 V (840.71%)0.0 V665.66 V (1386.79%)221948.6 WDrop High
50 mm²151 A118 A282.48 V (588.5%)0.0 V465.96 V (970.75%)155364.0 WDrop High
70 mm²192 A150 A201.77 V (420.36%)0.0 V332.83 V (693.39%)110974.3 WDrop High
95 mm²232 A181 A148.67 V (309.74%)0.0 V245.24 V (510.92%)81770.5 WDrop High
120 mm²269 A210 A117.7 V (245.21%)0.0 V194.15 V (404.48%)64735.0 WDrop High
150 mm²309 A241 A94.16 V (196.17%)0.0 V155.32 V (323.58%)51788.0 WDrop High
185 mm²353 A275 A76.35 V (159.05%)0.0 V125.94 V (262.36%)41990.3 WDrop High
240 mm²415 A324 A58.85 V (122.6%)0.0 V97.07 V (202.24%)32367.5 WDrop High
300 mm²477 A372 A47.08 V (98.08%)0.9 V77.66 V (161.79%)25894.0 WDrop High
400 mm²570 A445 A35.31 V (73.56%)12.7 V58.24 V (121.34%)19420.5 WDrop High

FAQ — 550 Amp Cable Size at 600 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 600 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25× 400 mm² copper cable for 550A over 600m at 48V (voltage drop: 1.41V or 2.94%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.