600 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 120 m (393.7 ft).
Copper Cable (≤3% Drop)11× 400 mm²Drop: 0.7V (2.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.71V (52.95%)
Voltage at Load23.3 VLine Loss: 420.2 W
Max Power & Breaker14.4 kW600A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 120m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2054.4 V (8560.0%) | 0.0 V | 3388.8 V (14120.0%) | 1232640.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1232.64 V (5136.0%) | 0.0 V | 2033.28 V (8472.0%) | 739584.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 770.4 V (3210.0%) | 0.0 V | 1270.8 V (5295.0%) | 462240.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 513.6 V (2140.0%) | 0.0 V | 847.2 V (3530.0%) | 308160.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 308.16 V (1284.0%) | 0.0 V | 508.32 V (2118.0%) | 184896.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 192.6 V (802.5%) | 0.0 V | 317.7 V (1323.75%) | 115560.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 123.26 V (513.6%) | 0.0 V | 203.33 V (847.2%) | 73958.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 88.05 V (366.86%) | 0.0 V | 145.23 V (605.14%) | 52827.4 W | Drop High |
| 50 mm² | 151 A | 118 A | 61.63 V (256.8%) | 0.0 V | 101.66 V (423.6%) | 36979.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 44.02 V (183.43%) | 0.0 V | 72.62 V (302.57%) | 26413.7 W | Drop High |
| 95 mm² | 232 A | 181 A | 32.44 V (135.16%) | 0.0 V | 53.51 V (222.95%) | 19462.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 25.68 V (107.0%) | 0.0 V | 42.36 V (176.5%) | 15408.0 W | Drop High |
| 150 mm² | 309 A | 241 A | 20.54 V (85.6%) | 3.5 V | 33.89 V (141.2%) | 12326.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 16.66 V (69.41%) | 7.3 V | 27.48 V (114.49%) | 9994.4 W | Drop High |
| 240 mm² | 415 A | 324 A | 12.84 V (53.5%) | 11.2 V | 21.18 V (88.25%) | 7704.0 W | Drop High |
| 300 mm² | 477 A | 372 A | 10.27 V (42.8%) | 13.7 V | 16.94 V (70.6%) | 6163.2 W | Drop High |
| 400 mm² | 570 A | 445 A | 7.7 V (32.1%) | 16.3 V | 12.71 V (52.95%) | 4622.4 W | Drop High |
FAQ — 600 Amp Cable Size at 120 Meters (24V DC (Off-Grid Solar / Industrial Control))
What mm² cable size is required for 600A at 120 meters (24V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 11× 400 mm² copper cable for 600A over 120m at 24V (voltage drop: 0.7V or 2.92%).
What is the power capacity of 600A at 24V?
At unity power factor, 600A at 24V supports 14.4 kW with a standard 600A circuit breaker.
Related Lengths & Currents (24V)
600A · 5m (24V)600A · 10m (24V)600A · 15m (24V)600A · 20m (24V)600A · 25m (24V)600A · 30m (24V)600A · 35m (24V)600A · 40m (24V)600A · 45m (24V)600A · 50m (24V)600A · 60m (24V)600A · 70m (24V)10A · 120m (24V)16A · 120m (24V)20A · 120m (24V)25A · 120m (24V)32A · 120m (24V)40A · 120m (24V)50A · 120m (24V)63A · 120m (24V)80A · 120m (24V)100A · 120m (24V)125A · 120m (24V)160A · 120m (24V)200A · 120m (24V)