600 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)14× 400 mm²Drop: 0.69V (2.87%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 15.88V (66.19%)
Voltage at Load23.3 VLine Loss: 412.7 W
Max Power & Breaker14.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2568.0 V (10700.0%)0.0 V4236.0 V (17650.0%)1540800.0 WDrop High
2.5 mm²24 A18 A1540.8 V (6420.0%)0.0 V2541.6 V (10590.0%)924480.0 WDrop High
4 mm²32 A25 A963.0 V (4012.5%)0.0 V1588.5 V (6618.75%)577800.0 WDrop High
6 mm²41 A32 A642.0 V (2675.0%)0.0 V1059.0 V (4412.5%)385200.0 WDrop High
10 mm²57 A44 A385.2 V (1605.0%)0.0 V635.4 V (2647.5%)231120.0 WDrop High
16 mm²76 A59 A240.75 V (1003.12%)0.0 V397.12 V (1654.69%)144450.0 WDrop High
25 mm²101 A78 A154.08 V (642.0%)0.0 V254.16 V (1059.0%)92448.0 WDrop High
35 mm²125 A97 A110.06 V (458.57%)0.0 V181.54 V (756.43%)66034.3 WDrop High
50 mm²151 A118 A77.04 V (321.0%)0.0 V127.08 V (529.5%)46224.0 WDrop High
70 mm²192 A150 A55.03 V (229.29%)0.0 V90.77 V (378.21%)33017.1 WDrop High
95 mm²232 A181 A40.55 V (168.95%)0.0 V66.88 V (278.68%)24328.4 WDrop High
120 mm²269 A210 A32.1 V (133.75%)0.0 V52.95 V (220.62%)19260.0 WDrop High
150 mm²309 A241 A25.68 V (107.0%)0.0 V42.36 V (176.5%)15408.0 WDrop High
185 mm²353 A275 A20.82 V (86.76%)3.2 V34.35 V (143.11%)12493.0 WDrop High
240 mm²415 A324 A16.05 V (66.88%)7.9 V26.47 V (110.31%)9630.0 WDrop High
300 mm²477 A372 A12.84 V (53.5%)11.2 V21.18 V (88.25%)7704.0 WDrop High
400 mm²570 A445 A9.63 V (40.12%)14.4 V15.88 V (66.19%)5778.0 WDrop High

FAQ — 600 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 600A at 150 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 14× 400 mm² copper cable for 600A over 150m at 24V (voltage drop: 0.69V or 2.87%).

What is the power capacity of 600A at 24V?

At unity power factor, 600A at 24V supports 14.4 kW with a standard 600A circuit breaker.