⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

25 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 25 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)240 mm²Drop: 0.67V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.66V (2.76%)
Voltage at Load23.3 VLine Loss: 16.7 W
Max Power & Breaker0.6 kW25A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 25A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A107.0 V (445.83%)0.0 V176.5 V (735.42%)2675.0 WDrop High
2.5 mm²24 A18 A64.2 V (267.5%)0.0 V105.9 V (441.25%)1605.0 WDrop High
4 mm²32 A25 A40.12 V (167.19%)0.0 V66.19 V (275.78%)1003.1 WDrop High
6 mm²41 A32 A26.75 V (111.46%)0.0 V44.12 V (183.85%)668.8 WDrop High
10 mm²57 A44 A16.05 V (66.88%)7.9 V26.47 V (110.31%)401.2 WDrop High
16 mm²76 A59 A10.03 V (41.8%)14.0 V16.55 V (68.95%)250.8 WDrop High
25 mm²101 A78 A6.42 V (26.75%)17.6 V10.59 V (44.12%)160.5 WDrop High
35 mm²125 A97 A4.59 V (19.11%)19.4 V7.56 V (31.52%)114.6 WDrop High
50 mm²151 A118 A3.21 V (13.37%)20.8 V5.29 V (22.06%)80.2 WDrop High
70 mm²192 A150 A2.29 V (9.55%)21.7 V3.78 V (15.76%)57.3 WDrop High
95 mm²232 A181 A1.69 V (7.04%)22.3 V2.79 V (11.61%)42.2 WDrop High
120 mm²269 A210 A1.34 V (5.57%)22.7 V2.21 V (9.19%)33.4 WDrop High
150 mm²309 A241 A1.07 V (4.46%)22.9 V1.76 V (7.35%)26.8 W~ ≤5%
185 mm²353 A275 A0.87 V (3.61%)23.1 V1.43 V (5.96%)21.7 W~ ≤5%
240 mm²415 A324 A0.67 V (2.79%)23.3 V1.1 V (4.6%)16.7 W✓ OK (≤3%)
300 mm²477 A372 A0.53 V (2.23%)23.5 V0.88 V (3.68%)13.4 W✓ OK (≤3%)
400 mm²570 A445 A0.4 V (1.67%)23.6 V0.66 V (2.76%)10.0 W✓ OK (≤3%)

FAQ — 25 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 25A at 150 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 240 mm² copper cable for 25A over 150m at 24V (voltage drop: 0.67V or 2.79%).

What is the power capacity of 25A at 24V?

At unity power factor, 25A at 24V supports 0.6 kW with a standard 25A circuit breaker.