80 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.64V (2.67%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.12V (8.82%)
Voltage at Load23.4 VLine Loss: 51.4 W
Max Power & Breaker1.92 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A342.4 V (1426.67%)0.0 V564.8 V (2353.33%)27392.0 WDrop High
2.5 mm²24 A18 A205.44 V (856.0%)0.0 V338.88 V (1412.0%)16435.2 WDrop High
4 mm²32 A25 A128.4 V (535.0%)0.0 V211.8 V (882.5%)10272.0 WDrop High
6 mm²41 A32 A85.6 V (356.67%)0.0 V141.2 V (588.33%)6848.0 WDrop High
10 mm²57 A44 A51.36 V (214.0%)0.0 V84.72 V (353.0%)4108.8 WDrop High
16 mm²76 A59 A32.1 V (133.75%)0.0 V52.95 V (220.63%)2568.0 WDrop High
25 mm²101 A78 A20.54 V (85.6%)3.5 V33.89 V (141.2%)1643.5 WDrop High
35 mm²125 A97 A14.67 V (61.14%)9.3 V24.21 V (100.86%)1173.9 WDrop High
50 mm²151 A118 A10.27 V (42.8%)13.7 V16.94 V (70.6%)821.8 WDrop High
70 mm²192 A150 A7.34 V (30.57%)16.7 V12.1 V (50.43%)587.0 WDrop High
95 mm²232 A181 A5.41 V (22.53%)18.6 V8.92 V (37.16%)432.5 WDrop High
120 mm²269 A210 A4.28 V (17.83%)19.7 V7.06 V (29.42%)342.4 WDrop High
150 mm²309 A241 A3.42 V (14.27%)20.6 V5.65 V (23.53%)273.9 WDrop High
185 mm²353 A275 A2.78 V (11.57%)21.2 V4.58 V (19.08%)222.1 WDrop High
240 mm²415 A324 A2.14 V (8.92%)21.9 V3.53 V (14.71%)171.2 WDrop High
300 mm²477 A372 A1.71 V (7.13%)22.3 V2.82 V (11.77%)137.0 WDrop High
400 mm²570 A445 A1.28 V (5.35%)22.7 V2.12 V (8.82%)102.7 WDrop High

FAQ — 80 Amp Cable Size at 150 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 80A at 150 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 80A over 150m at 24V (voltage drop: 0.64V or 2.67%).

What is the power capacity of 80A at 24V?

At unity power factor, 80A at 24V supports 1.92 kW with a standard 80A circuit breaker.