63 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 63 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 11.68V (1.69%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 12.33V (1.79%)
Voltage at Load678.3 VLine Loss: 1274.0 W
Max Power & Breaker75.29 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A124.54 V (18.05%)565.5 V205.44 V (29.77%)13589.9 WDrop High
2.5 mm²24 A18 A74.72 V (10.83%)615.3 V123.26 V (17.86%)8153.9 WDrop High
4 mm²32 A25 A46.7 V (6.77%)643.3 V77.04 V (11.16%)5096.2 WDrop High
6 mm²41 A32 A31.14 V (4.51%)658.9 V51.36 V (7.44%)3397.5 WDrop High
10 mm²57 A44 A18.68 V (2.71%)671.3 V30.82 V (4.47%)2038.5 WDrop High
16 mm²76 A59 A11.68 V (1.69%)678.3 V19.26 V (2.79%)1274.0 W✓ OK (≤3%)
25 mm²101 A78 A7.47 V (1.08%)682.5 V12.33 V (1.79%)815.4 W✓ OK (≤3%)
35 mm²125 A97 A5.34 V (0.77%)684.7 V8.8 V (1.28%)582.4 W✓ OK (≤3%)
50 mm²151 A118 A3.74 V (0.54%)686.3 V6.16 V (0.89%)407.7 W✓ OK (≤3%)
70 mm²192 A150 A2.67 V (0.39%)687.3 V4.4 V (0.64%)291.2 W✓ OK (≤3%)
95 mm²232 A181 A1.97 V (0.28%)688.0 V3.24 V (0.47%)214.6 W✓ OK (≤3%)
120 mm²269 A210 A1.56 V (0.23%)688.4 V2.57 V (0.37%)169.9 W✓ OK (≤3%)
150 mm²309 A241 A1.25 V (0.18%)688.8 V2.05 V (0.3%)135.9 W✓ OK (≤3%)
185 mm²353 A275 A1.01 V (0.15%)689.0 V1.67 V (0.24%)110.2 W✓ OK (≤3%)
240 mm²415 A324 A0.78 V (0.11%)689.2 V1.28 V (0.19%)84.9 W✓ OK (≤3%)
300 mm²477 A372 A0.62 V (0.09%)689.4 V1.03 V (0.15%)67.9 W✓ OK (≤3%)
400 mm²570 A445 A0.47 V (0.07%)689.5 V0.77 V (0.11%)51.0 W✓ OK (≤3%)

FAQ — 63 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 63A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 63A over 80m at 690V (voltage drop: 11.68V or 1.69%).

What is the power capacity of 63A at 690V?

At unity power factor, 63A at 690V supports 75.29 kW with a standard 63A circuit breaker.