80 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 80 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 9.49V (1.38%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 11.18V (1.62%)
Voltage at Load680.5 VLine Loss: 1314.8 W
Max Power & Breaker95.61 kW80A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 80A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A158.15 V (22.92%)531.9 V260.87 V (37.81%)21913.6 WDrop High
2.5 mm²24 A18 A94.89 V (13.75%)595.1 V156.52 V (22.68%)13148.2 WDrop High
4 mm²32 A25 A59.31 V (8.59%)630.7 V97.83 V (14.18%)8217.6 WDrop High
6 mm²41 A32 A39.54 V (5.73%)650.5 V65.22 V (9.45%)5478.4 WDrop High
10 mm²57 A44 A23.72 V (3.44%)666.3 V39.13 V (5.67%)3287.0 WDrop High
16 mm²76 A59 A14.83 V (2.15%)675.2 V24.46 V (3.54%)2054.4 WDrop High
25 mm²101 A78 A9.49 V (1.38%)680.5 V15.65 V (2.27%)1314.8 W✓ OK (≤3%)
35 mm²125 A97 A6.78 V (0.98%)683.2 V11.18 V (1.62%)939.2 W✓ OK (≤3%)
50 mm²151 A118 A4.74 V (0.69%)685.3 V7.83 V (1.13%)657.4 W✓ OK (≤3%)
70 mm²192 A150 A3.39 V (0.49%)686.6 V5.59 V (0.81%)469.6 W✓ OK (≤3%)
95 mm²232 A181 A2.5 V (0.36%)687.5 V4.12 V (0.6%)346.0 W✓ OK (≤3%)
120 mm²269 A210 A1.98 V (0.29%)688.0 V3.26 V (0.47%)273.9 W✓ OK (≤3%)
150 mm²309 A241 A1.58 V (0.23%)688.4 V2.61 V (0.38%)219.1 W✓ OK (≤3%)
185 mm²353 A275 A1.28 V (0.19%)688.7 V2.12 V (0.31%)177.7 W✓ OK (≤3%)
240 mm²415 A324 A0.99 V (0.14%)689.0 V1.63 V (0.24%)137.0 W✓ OK (≤3%)
300 mm²477 A372 A0.79 V (0.11%)689.2 V1.3 V (0.19%)109.6 W✓ OK (≤3%)
400 mm²570 A445 A0.59 V (0.09%)689.4 V0.98 V (0.14%)82.2 W✓ OK (≤3%)

FAQ — 80 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 80A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 80A over 80m at 690V (voltage drop: 9.49V or 1.38%).

What is the power capacity of 80A at 690V?

At unity power factor, 80A at 690V supports 95.61 kW with a standard 80A circuit breaker.