⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

32 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)6 mm²Drop: 15.81V (2.29%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 15.65V (2.27%)
Voltage at Load674.2 VLine Loss: 876.5 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A63.26 V (9.17%)626.7 V104.35 V (15.12%)3506.2 WDrop High
2.5 mm²24 A18 A37.96 V (5.5%)652.0 V62.61 V (9.07%)2103.7 WDrop High
4 mm²32 A25 A23.72 V (3.44%)666.3 V39.13 V (5.67%)1314.8 W~ ≤5%
6 mm²41 A32 A15.81 V (2.29%)674.2 V26.09 V (3.78%)876.5 W✓ OK (≤3%)
10 mm²57 A44 A9.49 V (1.38%)680.5 V15.65 V (2.27%)525.9 W✓ OK (≤3%)
16 mm²76 A59 A5.93 V (0.86%)684.1 V9.78 V (1.42%)328.7 W✓ OK (≤3%)
25 mm²101 A78 A3.8 V (0.55%)686.2 V6.26 V (0.91%)210.4 W✓ OK (≤3%)
35 mm²125 A97 A2.71 V (0.39%)687.3 V4.47 V (0.65%)150.3 W✓ OK (≤3%)
50 mm²151 A118 A1.9 V (0.28%)688.1 V3.13 V (0.45%)105.2 W✓ OK (≤3%)
70 mm²192 A150 A1.36 V (0.2%)688.6 V2.24 V (0.32%)75.1 W✓ OK (≤3%)
95 mm²232 A181 A1.0 V (0.14%)689.0 V1.65 V (0.24%)55.4 W✓ OK (≤3%)
120 mm²269 A210 A0.79 V (0.11%)689.2 V1.3 V (0.19%)43.8 W✓ OK (≤3%)
150 mm²309 A241 A0.63 V (0.09%)689.4 V1.04 V (0.15%)35.1 W✓ OK (≤3%)
185 mm²353 A275 A0.51 V (0.07%)689.5 V0.85 V (0.12%)28.4 W✓ OK (≤3%)
240 mm²415 A324 A0.4 V (0.06%)689.6 V0.65 V (0.09%)21.9 W✓ OK (≤3%)
300 mm²477 A372 A0.32 V (0.05%)689.7 V0.52 V (0.08%)17.5 W✓ OK (≤3%)
400 mm²570 A445 A0.24 V (0.03%)689.8 V0.39 V (0.06%)13.1 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 6 mm² copper cable for 32A over 80m at 690V (voltage drop: 15.81V or 2.29%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.