16 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 16 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2.5 mm²Drop: 18.98V (2.75%)
Aluminum Cable (≤3% Drop)4 mm²Drop: 19.57V (2.84%)
Voltage at Load671.0 VLine Loss: 525.9 W
Max Power & Breaker19.12 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A31.63 V (4.58%)658.4 V52.17 V (7.56%)876.5 W~ ≤5%
2.5 mm²24 A18 A18.98 V (2.75%)671.0 V31.3 V (4.54%)525.9 W✓ OK (≤3%)
4 mm²32 A25 A11.86 V (1.72%)678.1 V19.57 V (2.84%)328.7 W✓ OK (≤3%)
6 mm²41 A32 A7.91 V (1.15%)682.1 V13.04 V (1.89%)219.1 W✓ OK (≤3%)
10 mm²57 A44 A4.74 V (0.69%)685.3 V7.83 V (1.13%)131.5 W✓ OK (≤3%)
16 mm²76 A59 A2.97 V (0.43%)687.0 V4.89 V (0.71%)82.2 W✓ OK (≤3%)
25 mm²101 A78 A1.9 V (0.28%)688.1 V3.13 V (0.45%)52.6 W✓ OK (≤3%)
35 mm²125 A97 A1.36 V (0.2%)688.6 V2.24 V (0.32%)37.6 W✓ OK (≤3%)
50 mm²151 A118 A0.95 V (0.14%)689.1 V1.57 V (0.23%)26.3 W✓ OK (≤3%)
70 mm²192 A150 A0.68 V (0.1%)689.3 V1.12 V (0.16%)18.8 W✓ OK (≤3%)
95 mm²232 A181 A0.5 V (0.07%)689.5 V0.82 V (0.12%)13.8 W✓ OK (≤3%)
120 mm²269 A210 A0.4 V (0.06%)689.6 V0.65 V (0.09%)11.0 W✓ OK (≤3%)
150 mm²309 A241 A0.32 V (0.05%)689.7 V0.52 V (0.08%)8.8 W✓ OK (≤3%)
185 mm²353 A275 A0.26 V (0.04%)689.7 V0.42 V (0.06%)7.1 W✓ OK (≤3%)
240 mm²415 A324 A0.2 V (0.03%)689.8 V0.33 V (0.05%)5.5 W✓ OK (≤3%)
300 mm²477 A372 A0.16 V (0.02%)689.8 V0.26 V (0.04%)4.4 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.02%)689.9 V0.2 V (0.03%)3.3 W✓ OK (≤3%)

FAQ — 16 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 16A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2.5 mm² copper cable for 16A over 80m at 690V (voltage drop: 18.98V or 2.75%).

What is the power capacity of 16A at 690V?

At unity power factor, 16A at 690V supports 19.12 kW with a standard 16A circuit breaker.