⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.14V (0.17%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.74V (0.54%)
Voltage at Load688.9 VLine Loss: 1376.3 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A605.41 V (87.74%)84.6 V998.64 V (144.73%)734020.0 WDrop High
2.5 mm²24 A18 A363.25 V (52.64%)326.8 V599.19 V (86.84%)440412.0 WDrop High
4 mm²32 A25 A227.03 V (32.9%)463.0 V374.49 V (54.27%)275257.5 WDrop High
6 mm²41 A32 A151.35 V (21.94%)538.6 V249.66 V (36.18%)183505.0 WDrop High
10 mm²57 A44 A90.81 V (13.16%)599.2 V149.8 V (21.71%)110103.0 WDrop High
16 mm²76 A59 A56.76 V (8.23%)633.2 V93.62 V (13.57%)68814.4 WDrop High
25 mm²101 A78 A36.32 V (5.26%)653.7 V59.92 V (8.68%)44041.2 WDrop High
35 mm²125 A97 A25.95 V (3.76%)664.1 V42.8 V (6.2%)31458.0 WDrop High
50 mm²151 A118 A18.16 V (2.63%)671.8 V29.96 V (4.34%)22020.6 WDrop High
70 mm²192 A150 A12.97 V (1.88%)677.0 V21.4 V (3.1%)15729.0 WDrop High
95 mm²232 A181 A9.56 V (1.39%)680.4 V15.77 V (2.29%)11589.8 WDrop High
120 mm²269 A210 A7.57 V (1.1%)682.4 V12.48 V (1.81%)9175.2 WDrop High
150 mm²309 A241 A6.05 V (0.88%)683.9 V9.99 V (1.45%)7340.2 WDrop High
185 mm²353 A275 A4.91 V (0.71%)685.1 V8.1 V (1.17%)5951.5 WDrop High
240 mm²415 A324 A3.78 V (0.55%)686.2 V6.24 V (0.9%)4587.6 WDrop High
300 mm²477 A372 A3.03 V (0.44%)687.0 V4.99 V (0.72%)3670.1 WDrop High
400 mm²570 A445 A2.27 V (0.33%)687.7 V3.74 V (0.54%)2752.6 WDrop High

FAQ — 700 Amp Cable Size at 35 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 35 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 35m at 690V (voltage drop: 1.14V or 0.17%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.