700 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 50 m (164.0 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.62V (0.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.35V (0.78%)
Voltage at Load688.4 VLine Loss: 1966.1 W
Max Power & Breaker836.58 kW700A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 50m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 864.87 V (125.34%) | 0.0 V | 1426.63 V (206.76%) | 1048600.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 518.92 V (75.21%) | 171.1 V | 855.98 V (124.06%) | 629160.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 324.33 V (47.0%) | 365.7 V | 534.99 V (77.53%) | 393225.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 216.22 V (31.34%) | 473.8 V | 356.66 V (51.69%) | 262150.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 129.73 V (18.8%) | 560.3 V | 213.99 V (31.01%) | 157290.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 81.08 V (11.75%) | 608.9 V | 133.75 V (19.38%) | 98306.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 51.89 V (7.52%) | 638.1 V | 85.6 V (12.41%) | 62916.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 37.07 V (5.37%) | 652.9 V | 61.14 V (8.86%) | 44940.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 25.95 V (3.76%) | 664.1 V | 42.8 V (6.2%) | 31458.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 18.53 V (2.69%) | 671.5 V | 30.57 V (4.43%) | 22470.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 13.66 V (1.98%) | 676.3 V | 22.53 V (3.26%) | 16556.8 W | Drop High |
| 120 mm² | 269 A | 210 A | 10.81 V (1.57%) | 679.2 V | 17.83 V (2.58%) | 13107.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 8.65 V (1.25%) | 681.4 V | 14.27 V (2.07%) | 10486.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 7.01 V (1.02%) | 683.0 V | 11.57 V (1.68%) | 8502.2 W | Drop High |
| 240 mm² | 415 A | 324 A | 5.41 V (0.78%) | 684.6 V | 8.92 V (1.29%) | 6553.7 W | Drop High |
| 300 mm² | 477 A | 372 A | 4.32 V (0.63%) | 685.7 V | 7.13 V (1.03%) | 5243.0 W | Drop High |
| 400 mm² | 570 A | 445 A | 3.24 V (0.47%) | 686.8 V | 5.35 V (0.78%) | 3932.2 W | Drop High |
FAQ — 700 Amp Cable Size at 50 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 700A at 50 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 50m at 690V (voltage drop: 1.62V or 0.23%).
What is the power capacity of 700A at 690V?
At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.
Related Lengths & Currents (690V)
700A · 5m (690V)700A · 10m (690V)700A · 15m (690V)700A · 20m (690V)700A · 25m (690V)700A · 30m (690V)700A · 35m (690V)700A · 40m (690V)700A · 45m (690V)700A · 60m (690V)700A · 70m (690V)10A · 50m (690V)16A · 50m (690V)20A · 50m (690V)25A · 50m (690V)32A · 50m (690V)40A · 50m (690V)50A · 50m (690V)63A · 50m (690V)80A · 50m (690V)100A · 50m (690V)125A · 50m (690V)160A · 50m (690V)200A · 50m (690V)