700 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.27V (0.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.49V (1.09%)
Voltage at Load687.7 VLine Loss: 2752.6 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1210.82 V (175.48%)0.0 V1997.29 V (289.46%)1468040.0 WDrop High
2.5 mm²24 A18 A726.49 V (105.29%)0.0 V1198.37 V (173.68%)880824.0 WDrop High
4 mm²32 A25 A454.06 V (65.81%)235.9 V748.98 V (108.55%)550515.0 WDrop High
6 mm²41 A32 A302.7 V (43.87%)387.3 V499.32 V (72.37%)367010.0 WDrop High
10 mm²57 A44 A181.62 V (26.32%)508.4 V299.59 V (43.42%)220206.0 WDrop High
16 mm²76 A59 A113.51 V (16.45%)576.5 V187.25 V (27.14%)137628.8 WDrop High
25 mm²101 A78 A72.65 V (10.53%)617.4 V119.84 V (17.37%)88082.4 WDrop High
35 mm²125 A97 A51.89 V (7.52%)638.1 V85.6 V (12.41%)62916.0 WDrop High
50 mm²151 A118 A36.32 V (5.26%)653.7 V59.92 V (8.68%)44041.2 WDrop High
70 mm²192 A150 A25.95 V (3.76%)664.1 V42.8 V (6.2%)31458.0 WDrop High
95 mm²232 A181 A19.12 V (2.77%)670.9 V31.54 V (4.57%)23179.6 WDrop High
120 mm²269 A210 A15.14 V (2.19%)674.9 V24.97 V (3.62%)18350.5 WDrop High
150 mm²309 A241 A12.11 V (1.75%)677.9 V19.97 V (2.89%)14680.4 WDrop High
185 mm²353 A275 A9.82 V (1.42%)680.2 V16.19 V (2.35%)11903.0 WDrop High
240 mm²415 A324 A7.57 V (1.1%)682.4 V12.48 V (1.81%)9175.2 WDrop High
300 mm²477 A372 A6.05 V (0.88%)683.9 V9.99 V (1.45%)7340.2 WDrop High
400 mm²570 A445 A4.54 V (0.66%)685.5 V7.49 V (1.09%)5505.2 WDrop High

FAQ — 700 Amp Cable Size at 70 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 70 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 70m at 690V (voltage drop: 2.27V or 0.33%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.