700 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.16V (0.03%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.53V (0.08%)
Voltage at Load689.8 VLine Loss: 196.6 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A86.49 V (12.53%)603.5 V142.66 V (20.68%)104860.0 WDrop High
2.5 mm²24 A18 A51.89 V (7.52%)638.1 V85.6 V (12.41%)62916.0 WDrop High
4 mm²32 A25 A32.43 V (4.7%)657.6 V53.5 V (7.75%)39322.5 WDrop High
6 mm²41 A32 A21.62 V (3.13%)668.4 V35.67 V (5.17%)26215.0 WDrop High
10 mm²57 A44 A12.97 V (1.88%)677.0 V21.4 V (3.1%)15729.0 WDrop High
16 mm²76 A59 A8.11 V (1.18%)681.9 V13.37 V (1.94%)9830.6 WDrop High
25 mm²101 A78 A5.19 V (0.75%)684.8 V8.56 V (1.24%)6291.6 WDrop High
35 mm²125 A97 A3.71 V (0.54%)686.3 V6.11 V (0.89%)4494.0 WDrop High
50 mm²151 A118 A2.59 V (0.38%)687.4 V4.28 V (0.62%)3145.8 WDrop High
70 mm²192 A150 A1.85 V (0.27%)688.1 V3.06 V (0.44%)2247.0 WDrop High
95 mm²232 A181 A1.37 V (0.2%)688.6 V2.25 V (0.33%)1655.7 WDrop High
120 mm²269 A210 A1.08 V (0.16%)688.9 V1.78 V (0.26%)1310.8 WDrop High
150 mm²309 A241 A0.86 V (0.13%)689.1 V1.43 V (0.21%)1048.6 WDrop High
185 mm²353 A275 A0.7 V (0.1%)689.3 V1.16 V (0.17%)850.2 WDrop High
240 mm²415 A324 A0.54 V (0.08%)689.5 V0.89 V (0.13%)655.4 WDrop High
300 mm²477 A372 A0.43 V (0.06%)689.6 V0.71 V (0.1%)524.3 WDrop High
400 mm²570 A445 A0.32 V (0.05%)689.7 V0.53 V (0.08%)393.2 WDrop High

FAQ — 700 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 5m at 690V (voltage drop: 0.16V or 0.03%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.