750 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.08V (0.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.06V (2.91%)
Voltage at Load683.9 VLine Loss: 7899.6 W
Max Power & Breaker896.34 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3243.27 V (470.04%)0.0 V5349.87 V (775.34%)4213125.0 WDrop High
2.5 mm²24 A18 A1945.96 V (282.02%)0.0 V3209.92 V (465.21%)2527875.0 WDrop High
4 mm²32 A25 A1216.22 V (176.26%)0.0 V2006.2 V (290.75%)1579921.9 WDrop High
6 mm²41 A32 A810.82 V (117.51%)0.0 V1337.47 V (193.84%)1053281.2 WDrop High
10 mm²57 A44 A486.49 V (70.51%)203.5 V802.48 V (116.3%)631968.7 WDrop High
16 mm²76 A59 A304.06 V (44.07%)385.9 V501.55 V (72.69%)394980.5 WDrop High
25 mm²101 A78 A194.6 V (28.2%)495.4 V320.99 V (46.52%)252787.5 WDrop High
35 mm²125 A97 A139.0 V (20.14%)551.0 V229.28 V (33.23%)180562.5 WDrop High
50 mm²151 A118 A97.3 V (14.1%)592.7 V160.5 V (23.26%)126393.7 WDrop High
70 mm²192 A150 A69.5 V (10.07%)620.5 V114.64 V (16.61%)90281.2 WDrop High
95 mm²232 A181 A51.21 V (7.42%)638.8 V84.47 V (12.24%)66523.0 WDrop High
120 mm²269 A210 A40.54 V (5.88%)649.5 V66.87 V (9.69%)52664.1 WDrop High
150 mm²309 A241 A32.43 V (4.7%)657.6 V53.5 V (7.75%)42131.2 WDrop High
185 mm²353 A275 A26.3 V (3.81%)663.7 V43.38 V (6.29%)34160.5 WDrop High
240 mm²415 A324 A20.27 V (2.94%)669.7 V33.44 V (4.85%)26332.0 WDrop High
300 mm²477 A372 A16.22 V (2.35%)673.8 V26.75 V (3.88%)21065.6 WDrop High
400 mm²570 A445 A12.16 V (1.76%)677.8 V20.06 V (2.91%)15799.2 WDrop High

FAQ — 750 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 750A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 175m at 690V (voltage drop: 6.08V or 0.88%).

What is the power capacity of 750A at 690V?

At unity power factor, 750A at 690V supports 896.34 kW with a standard 800A circuit breaker.