750 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.69V (0.1%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.29V (0.33%)
Voltage at Load689.3 VLine Loss: 902.8 W
Max Power & Breaker896.34 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A370.66 V (53.72%)319.3 V611.41 V (88.61%)481500.0 WDrop High
2.5 mm²24 A18 A222.4 V (32.23%)467.6 V366.85 V (53.17%)288900.0 WDrop High
4 mm²32 A25 A139.0 V (20.14%)551.0 V229.28 V (33.23%)180562.5 WDrop High
6 mm²41 A32 A92.66 V (13.43%)597.3 V152.85 V (22.15%)120375.0 WDrop High
10 mm²57 A44 A55.6 V (8.06%)634.4 V91.71 V (13.29%)72225.0 WDrop High
16 mm²76 A59 A34.75 V (5.04%)655.3 V57.32 V (8.31%)45140.6 WDrop High
25 mm²101 A78 A22.24 V (3.22%)667.8 V36.68 V (5.32%)28890.0 WDrop High
35 mm²125 A97 A15.89 V (2.3%)674.1 V26.2 V (3.8%)20635.7 WDrop High
50 mm²151 A118 A11.12 V (1.61%)678.9 V18.34 V (2.66%)14445.0 WDrop High
70 mm²192 A150 A7.94 V (1.15%)682.1 V13.1 V (1.9%)10317.9 WDrop High
95 mm²232 A181 A5.85 V (0.85%)684.1 V9.65 V (1.4%)7602.6 WDrop High
120 mm²269 A210 A4.63 V (0.67%)685.4 V7.64 V (1.11%)6018.8 WDrop High
150 mm²309 A241 A3.71 V (0.54%)686.3 V6.11 V (0.89%)4815.0 WDrop High
185 mm²353 A275 A3.01 V (0.44%)687.0 V4.96 V (0.72%)3904.1 WDrop High
240 mm²415 A324 A2.32 V (0.34%)687.7 V3.82 V (0.55%)3009.4 WDrop High
300 mm²477 A372 A1.85 V (0.27%)688.1 V3.06 V (0.44%)2407.5 WDrop High
400 mm²570 A445 A1.39 V (0.2%)688.6 V2.29 V (0.33%)1805.6 WDrop High

FAQ — 750 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 750A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 20m at 690V (voltage drop: 0.69V or 0.1%).

What is the power capacity of 750A at 690V?

At unity power factor, 750A at 690V supports 896.34 kW with a standard 800A circuit breaker.