750 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.69V (1.26%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 28.66V (4.15%)
Voltage at Load681.3 VLine Loss: 11285.1 W
Max Power & Breaker896.34 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4633.24 V (671.48%)0.0 V7642.67 V (1107.63%)6018750.0 WDrop High
2.5 mm²24 A18 A2779.94 V (402.89%)0.0 V4585.6 V (664.58%)3611250.0 WDrop High
4 mm²32 A25 A1737.46 V (251.81%)0.0 V2866.0 V (415.36%)2257031.2 WDrop High
6 mm²41 A32 A1158.31 V (167.87%)0.0 V1910.67 V (276.91%)1504687.5 WDrop High
10 mm²57 A44 A694.99 V (100.72%)0.0 V1146.4 V (166.15%)902812.5 WDrop High
16 mm²76 A59 A434.37 V (62.95%)255.6 V716.5 V (103.84%)564257.8 WDrop High
25 mm²101 A78 A277.99 V (40.29%)412.0 V458.56 V (66.46%)361125.0 WDrop High
35 mm²125 A97 A198.57 V (28.78%)491.4 V327.54 V (47.47%)257946.4 WDrop High
50 mm²151 A118 A139.0 V (20.14%)551.0 V229.28 V (33.23%)180562.5 WDrop High
70 mm²192 A150 A99.28 V (14.39%)590.7 V163.77 V (23.74%)128973.2 WDrop High
95 mm²232 A181 A73.16 V (10.6%)616.8 V120.67 V (17.49%)95032.9 WDrop High
120 mm²269 A210 A57.92 V (8.39%)632.1 V95.53 V (13.85%)75234.4 WDrop High
150 mm²309 A241 A46.33 V (6.71%)643.7 V76.43 V (11.08%)60187.5 WDrop High
185 mm²353 A275 A37.57 V (5.44%)652.4 V61.97 V (8.98%)48800.7 WDrop High
240 mm²415 A324 A28.96 V (4.2%)661.0 V47.77 V (6.92%)37617.2 WDrop High
300 mm²477 A372 A23.17 V (3.36%)666.8 V38.21 V (5.54%)30093.8 WDrop High
400 mm²570 A445 A17.37 V (2.52%)672.6 V28.66 V (4.15%)22570.3 WDrop High

FAQ — 750 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 750A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 250m at 690V (voltage drop: 8.69V or 1.26%).

What is the power capacity of 750A at 690V?

At unity power factor, 750A at 690V supports 896.34 kW with a standard 800A circuit breaker.