750 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 12.16V (1.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 40.12V (5.82%)
Voltage at Load677.8 VLine Loss: 15799.2 W
Max Power & Breaker896.34 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6486.53 V (940.08%)0.0 V10699.74 V (1550.69%)8426250.0 WDrop High
2.5 mm²24 A18 A3891.92 V (564.05%)0.0 V6419.85 V (930.41%)5055750.0 WDrop High
4 mm²32 A25 A2432.45 V (352.53%)0.0 V4012.4 V (581.51%)3159843.7 WDrop High
6 mm²41 A32 A1621.63 V (235.02%)0.0 V2674.94 V (387.67%)2106562.5 WDrop High
10 mm²57 A44 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)1263937.5 WDrop High
16 mm²76 A59 A608.11 V (88.13%)81.9 V1003.1 V (145.38%)789960.9 WDrop High
25 mm²101 A78 A389.19 V (56.4%)300.8 V641.98 V (93.04%)505575.0 WDrop High
35 mm²125 A97 A277.99 V (40.29%)412.0 V458.56 V (66.46%)361125.0 WDrop High
50 mm²151 A118 A194.6 V (28.2%)495.4 V320.99 V (46.52%)252787.5 WDrop High
70 mm²192 A150 A139.0 V (20.14%)551.0 V229.28 V (33.23%)180562.5 WDrop High
95 mm²232 A181 A102.42 V (14.84%)587.6 V168.94 V (24.48%)133046.1 WDrop High
120 mm²269 A210 A81.08 V (11.75%)608.9 V133.75 V (19.38%)105328.1 WDrop High
150 mm²309 A241 A64.87 V (9.4%)625.1 V107.0 V (15.51%)84262.5 WDrop High
185 mm²353 A275 A52.59 V (7.62%)637.4 V86.75 V (12.57%)68320.9 WDrop High
240 mm²415 A324 A40.54 V (5.88%)649.5 V66.87 V (9.69%)52664.1 WDrop High
300 mm²477 A372 A32.43 V (4.7%)657.6 V53.5 V (7.75%)42131.2 WDrop High
400 mm²570 A445 A24.32 V (3.53%)665.7 V40.12 V (5.82%)31598.4 WDrop High

FAQ — 750 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 750A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 750A over 350m at 690V (voltage drop: 12.16V or 1.76%).

What is the power capacity of 750A at 690V?

At unity power factor, 750A at 690V supports 896.34 kW with a standard 800A circuit breaker.