⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

32 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 32 A over 60 m (196.9 ft).

Copper Cable (≤3% Drop)4 mm²Drop: 17.79V (2.58%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 19.57V (2.84%)
Voltage at Load672.2 VLine Loss: 986.1 W
Max Power & Breaker38.24 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A47.44 V (6.88%)642.6 V78.26 V (11.34%)2629.6 WDrop High
2.5 mm²24 A18 A28.47 V (4.13%)661.5 V46.96 V (6.81%)1577.8 WDrop High
4 mm²32 A25 A17.79 V (2.58%)672.2 V29.35 V (4.25%)986.1 W✓ OK (≤3%)
6 mm²41 A32 A11.86 V (1.72%)678.1 V19.57 V (2.84%)657.4 W✓ OK (≤3%)
10 mm²57 A44 A7.12 V (1.03%)682.9 V11.74 V (1.7%)394.4 W✓ OK (≤3%)
16 mm²76 A59 A4.45 V (0.64%)685.6 V7.34 V (1.06%)246.5 W✓ OK (≤3%)
25 mm²101 A78 A2.85 V (0.41%)687.2 V4.7 V (0.68%)157.8 W✓ OK (≤3%)
35 mm²125 A97 A2.03 V (0.29%)688.0 V3.35 V (0.49%)112.7 W✓ OK (≤3%)
50 mm²151 A118 A1.42 V (0.21%)688.6 V2.35 V (0.34%)78.9 W✓ OK (≤3%)
70 mm²192 A150 A1.02 V (0.15%)689.0 V1.68 V (0.24%)56.3 W✓ OK (≤3%)
95 mm²232 A181 A0.75 V (0.11%)689.3 V1.24 V (0.18%)41.5 W✓ OK (≤3%)
120 mm²269 A210 A0.59 V (0.09%)689.4 V0.98 V (0.14%)32.9 W✓ OK (≤3%)
150 mm²309 A241 A0.47 V (0.07%)689.5 V0.78 V (0.11%)26.3 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.06%)689.6 V0.63 V (0.09%)21.3 W✓ OK (≤3%)
240 mm²415 A324 A0.3 V (0.04%)689.7 V0.49 V (0.07%)16.4 W✓ OK (≤3%)
300 mm²477 A372 A0.24 V (0.03%)689.8 V0.39 V (0.06%)13.1 W✓ OK (≤3%)
400 mm²570 A445 A0.18 V (0.03%)689.8 V0.29 V (0.04%)9.9 W✓ OK (≤3%)

FAQ — 32 Amp Cable Size at 60 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 32A at 60 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4 mm² copper cable for 32A over 60m at 690V (voltage drop: 17.79V or 2.58%).

What is the power capacity of 32A at 690V?

At unity power factor, 32A at 690V supports 38.24 kW with a standard 32A circuit breaker.