800 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.12V (1.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 36.68V (5.32%)
Voltage at Load678.9 VLine Loss: 15408.0 W
Max Power & Breaker956.09 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5930.54 V (859.5%)0.0 V9782.62 V (1417.77%)8217600.0 WDrop High
2.5 mm²24 A18 A3558.33 V (515.7%)0.0 V5869.57 V (850.66%)4930560.0 WDrop High
4 mm²32 A25 A2223.95 V (322.31%)0.0 V3668.48 V (531.66%)3081600.0 WDrop High
6 mm²41 A32 A1482.64 V (214.87%)0.0 V2445.66 V (354.44%)2054400.0 WDrop High
10 mm²57 A44 A889.58 V (128.92%)0.0 V1467.39 V (212.67%)1232640.0 WDrop High
16 mm²76 A59 A555.99 V (80.58%)134.0 V917.12 V (132.92%)770400.0 WDrop High
25 mm²101 A78 A355.83 V (51.57%)334.2 V586.96 V (85.07%)493056.0 WDrop High
35 mm²125 A97 A254.17 V (36.84%)435.8 V419.26 V (60.76%)352182.9 WDrop High
50 mm²151 A118 A177.92 V (25.78%)512.1 V293.48 V (42.53%)246528.0 WDrop High
70 mm²192 A150 A127.08 V (18.42%)562.9 V209.63 V (30.38%)176091.4 WDrop High
95 mm²232 A181 A93.64 V (13.57%)596.4 V154.46 V (22.39%)129751.6 WDrop High
120 mm²269 A210 A74.13 V (10.74%)615.9 V122.28 V (17.72%)102720.0 WDrop High
150 mm²309 A241 A59.31 V (8.59%)630.7 V97.83 V (14.18%)82176.0 WDrop High
185 mm²353 A275 A48.09 V (6.97%)641.9 V79.32 V (11.5%)66629.2 WDrop High
240 mm²415 A324 A37.07 V (5.37%)652.9 V61.14 V (8.86%)51360.0 WDrop High
300 mm²477 A372 A29.65 V (4.3%)660.3 V48.91 V (7.09%)41088.0 WDrop High
400 mm²570 A445 A22.24 V (3.22%)667.8 V36.68 V (5.32%)30816.0 WDrop High

FAQ — 800 Amp Cable Size at 300 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 800A at 300 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 300m at 690V (voltage drop: 11.12V or 1.61%).

What is the power capacity of 800A at 690V?

At unity power factor, 800A at 690V supports 956.09 kW with a standard 800A circuit breaker.