900 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 5.0V (0.72%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.51V (2.39%)
Voltage at Load685.0 VLine Loss: 7800.3 W
Max Power & Breaker1075.6 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2668.74 V (386.77%)0.0 V4402.18 V (638.0%)4160160.0 WDrop High
2.5 mm²24 A18 A1601.25 V (232.06%)0.0 V2641.31 V (382.8%)2496096.0 WDrop High
4 mm²32 A25 A1000.78 V (145.04%)0.0 V1650.82 V (239.25%)1560060.0 WDrop High
6 mm²41 A32 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)1040040.0 WDrop High
10 mm²57 A44 A400.31 V (58.02%)289.7 V660.33 V (95.7%)624024.0 WDrop High
16 mm²76 A59 A250.19 V (36.26%)439.8 V412.7 V (59.81%)390015.0 WDrop High
25 mm²101 A78 A160.12 V (23.21%)529.9 V264.13 V (38.28%)249609.6 WDrop High
35 mm²125 A97 A114.37 V (16.58%)575.6 V188.66 V (27.34%)178292.6 WDrop High
50 mm²151 A118 A80.06 V (11.6%)609.9 V132.07 V (19.14%)124804.8 WDrop High
70 mm²192 A150 A57.19 V (8.29%)632.8 V94.33 V (13.67%)89146.3 WDrop High
95 mm²232 A181 A42.14 V (6.11%)647.9 V69.51 V (10.07%)65686.7 WDrop High
120 mm²269 A210 A33.36 V (4.83%)656.6 V55.03 V (7.97%)52002.0 WDrop High
150 mm²309 A241 A26.69 V (3.87%)663.3 V44.02 V (6.38%)41601.6 WDrop High
185 mm²353 A275 A21.64 V (3.14%)668.4 V35.69 V (5.17%)33731.0 WDrop High
240 mm²415 A324 A16.68 V (2.42%)673.3 V27.51 V (3.99%)26001.0 WDrop High
300 mm²477 A372 A13.34 V (1.93%)676.7 V22.01 V (3.19%)20800.8 WDrop High
400 mm²570 A445 A10.01 V (1.45%)680.0 V16.51 V (2.39%)15600.6 WDrop High

FAQ — 900 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 900A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 120m at 690V (voltage drop: 5.0V or 0.72%).

What is the power capacity of 900A at 690V?

At unity power factor, 900A at 690V supports 1075.6 kW with a standard 1000A circuit breaker.