900 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.83V (0.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.75V (0.4%)
Voltage at Load689.2 VLine Loss: 1300.0 W
Max Power & Breaker1075.6 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A444.79 V (64.46%)245.2 V733.7 V (106.33%)693360.0 WDrop High
2.5 mm²24 A18 A266.87 V (38.68%)423.1 V440.22 V (63.8%)416016.0 WDrop High
4 mm²32 A25 A166.8 V (24.17%)523.2 V275.14 V (39.87%)260010.0 WDrop High
6 mm²41 A32 A111.2 V (16.12%)578.8 V183.42 V (26.58%)173340.0 WDrop High
10 mm²57 A44 A66.72 V (9.67%)623.3 V110.05 V (15.95%)104004.0 WDrop High
16 mm²76 A59 A41.7 V (6.04%)648.3 V68.78 V (9.97%)65002.5 WDrop High
25 mm²101 A78 A26.69 V (3.87%)663.3 V44.02 V (6.38%)41601.6 WDrop High
35 mm²125 A97 A19.06 V (2.76%)670.9 V31.44 V (4.56%)29715.4 WDrop High
50 mm²151 A118 A13.34 V (1.93%)676.7 V22.01 V (3.19%)20800.8 WDrop High
70 mm²192 A150 A9.53 V (1.38%)680.5 V15.72 V (2.28%)14857.7 WDrop High
95 mm²232 A181 A7.02 V (1.02%)683.0 V11.58 V (1.68%)10947.8 WDrop High
120 mm²269 A210 A5.56 V (0.81%)684.4 V9.17 V (1.33%)8667.0 WDrop High
150 mm²309 A241 A4.45 V (0.64%)685.6 V7.34 V (1.06%)6933.6 WDrop High
185 mm²353 A275 A3.61 V (0.52%)686.4 V5.95 V (0.86%)5621.8 WDrop High
240 mm²415 A324 A2.78 V (0.4%)687.2 V4.59 V (0.66%)4333.5 WDrop High
300 mm²477 A372 A2.22 V (0.32%)687.8 V3.67 V (0.53%)3466.8 WDrop High
400 mm²570 A445 A1.67 V (0.24%)688.3 V2.75 V (0.4%)2600.1 WDrop High

FAQ — 900 Amp Cable Size at 20 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 900A at 20 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 20m at 690V (voltage drop: 0.83V or 0.12%).

What is the power capacity of 900A at 690V?

At unity power factor, 900A at 690V supports 1075.6 kW with a standard 1000A circuit breaker.