900 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 25 m (82.0 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.04V (0.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.44V (0.5%)
Voltage at Load689.0 VLine Loss: 1625.0 W
Max Power & Breaker1075.6 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 555.99 V (80.58%) | 134.0 V | 917.12 V (132.92%) | 866700.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 333.59 V (48.35%) | 356.4 V | 550.27 V (79.75%) | 520020.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 208.5 V (30.22%) | 481.5 V | 343.92 V (49.84%) | 325012.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 139.0 V (20.14%) | 551.0 V | 229.28 V (33.23%) | 216675.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 83.4 V (12.09%) | 606.6 V | 137.57 V (19.94%) | 130005.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 52.12 V (7.55%) | 637.9 V | 85.98 V (12.46%) | 81253.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 33.36 V (4.83%) | 656.6 V | 55.03 V (7.97%) | 52002.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 23.83 V (3.45%) | 666.2 V | 39.31 V (5.7%) | 37144.3 W | Drop High |
| 50 mm² | 151 A | 118 A | 16.68 V (2.42%) | 673.3 V | 27.51 V (3.99%) | 26001.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 11.91 V (1.73%) | 678.1 V | 19.65 V (2.85%) | 18572.1 W | Drop High |
| 95 mm² | 232 A | 181 A | 8.78 V (1.27%) | 681.2 V | 14.48 V (2.1%) | 13684.7 W | Drop High |
| 120 mm² | 269 A | 210 A | 6.95 V (1.01%) | 683.1 V | 11.46 V (1.66%) | 10833.7 W | Drop High |
| 150 mm² | 309 A | 241 A | 5.56 V (0.81%) | 684.4 V | 9.17 V (1.33%) | 8667.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 4.51 V (0.65%) | 685.5 V | 7.44 V (1.08%) | 7027.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 3.47 V (0.5%) | 686.5 V | 5.73 V (0.83%) | 5416.9 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.78 V (0.4%) | 687.2 V | 4.59 V (0.66%) | 4333.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 2.08 V (0.3%) | 687.9 V | 3.44 V (0.5%) | 3250.1 W | Drop High |
FAQ — 900 Amp Cable Size at 25 Meters (690V Three-Phase (Wind / Heavy Industrial))
What mm² cable size is required for 900A at 25 meters (690V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 25m at 690V (voltage drop: 1.04V or 0.15%).
What is the power capacity of 900A at 690V?
At unity power factor, 900A at 690V supports 1075.6 kW with a standard 1000A circuit breaker.
Related Lengths & Currents (690V)
900A · 5m (690V)900A · 10m (690V)900A · 15m (690V)900A · 20m (690V)900A · 30m (690V)900A · 35m (690V)900A · 40m (690V)900A · 45m (690V)900A · 50m (690V)900A · 60m (690V)900A · 70m (690V)10A · 25m (690V)16A · 25m (690V)20A · 25m (690V)25A · 25m (690V)32A · 25m (690V)40A · 25m (690V)50A · 25m (690V)63A · 25m (690V)80A · 25m (690V)100A · 25m (690V)125A · 25m (690V)160A · 25m (690V)200A · 25m (690V)