Kabeltværsnit for 10 Ampere ved 20 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 20 m ved 230V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 5.71V (2.48%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 5.65V (2.46%)
Voltage at Load224.3 VLine Loss: 57.1 W
Max Power & Breaker2.3 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 20m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 5.71 V (2.48%) | 224.3 V | 9.41 V (4.09%) | 57.1 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 3.42 V (1.49%) | 226.6 V | 5.65 V (2.46%) | 34.2 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 2.14 V (0.93%) | 227.9 V | 3.53 V (1.53%) | 21.4 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 1.43 V (0.62%) | 228.6 V | 2.35 V (1.02%) | 14.3 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 0.86 V (0.37%) | 229.1 V | 1.41 V (0.61%) | 8.6 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.54 V (0.23%) | 229.5 V | 0.88 V (0.38%) | 5.3 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 3.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.24 V (0.11%) | 229.8 V | 0.4 V (0.18%) | 2.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.17 V (0.07%) | 229.8 V | 0.28 V (0.12%) | 1.7 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.12 V (0.05%) | 229.9 V | 0.2 V (0.09%) | 1.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.09 V (0.04%) | 229.9 V | 0.15 V (0.06%) | 0.9 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.07 V (0.03%) | 229.9 V | 0.12 V (0.05%) | 0.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.06 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 0.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.05 V (0.02%) | 230.0 V | 0.08 V (0.03%) | 0.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.04 V (0.02%) | 230.0 V | 0.06 V (0.03%) | 0.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.03 V (0.01%) | 230.0 V | 0.05 V (0.02%) | 0.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.02 V (0.01%) | 230.0 V | 0.04 V (0.02%) | 0.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 10 Ampere ved 20 Meter (230V)
Hvilket kabeltværsnit kræves til 10A ved 20 meter (230V)?
Til 10 Ampere over 20 meter ved 230V anbefales 1.5 mm² kobberkabel (spændingsfald 5.71V / 2.48%).
Hvor mange kW svarer 10A ved 230V til?
Det svarer til 2.3 kW med en anbefalet sikring på 10A.
Related Lengths & Currents (230V)
10A · 5m (230V)10A · 10m (230V)10A · 15m (230V)10A · 25m (230V)10A · 30m (230V)10A · 35m (230V)10A · 40m (230V)10A · 45m (230V)10A · 50m (230V)10A · 60m (230V)10A · 70m (230V)16A · 20m (230V)20A · 20m (230V)25A · 20m (230V)32A · 20m (230V)40A · 20m (230V)50A · 20m (230V)63A · 20m (230V)80A · 20m (230V)100A · 20m (230V)125A · 20m (230V)160A · 20m (230V)200A · 20m (230V)