Kabeltværsnit for 10 Ampere ved 40 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 10 A over 40 m ved 230V.
Copper Cable (≤3% Drop)2.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.71V (2.05%)
Voltage at Load223.2 VLine Loss: 68.5 W
Max Power & Breaker2.3 kW10A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 10A at 40m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 11.41 V (4.96%) | 218.6 V | 18.83 V (8.19%) | 114.1 W | ~ ≤5% |
| 2.5 mm² | 24 A | 18 A | 6.85 V (2.98%) | 223.2 V | 11.3 V (4.91%) | 68.5 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 4.28 V (1.86%) | 225.7 V | 7.06 V (3.07%) | 42.8 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.85 V (1.24%) | 227.1 V | 4.71 V (2.05%) | 28.5 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.71 V (0.74%) | 228.3 V | 2.82 V (1.23%) | 17.1 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 1.07 V (0.47%) | 228.9 V | 1.76 V (0.77%) | 10.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.68 V (0.3%) | 229.3 V | 1.13 V (0.49%) | 6.8 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.49 V (0.21%) | 229.5 V | 0.81 V (0.35%) | 4.9 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.34 V (0.15%) | 229.7 V | 0.56 V (0.25%) | 3.4 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.24 V (0.11%) | 229.8 V | 0.4 V (0.18%) | 2.4 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.18 V (0.08%) | 229.8 V | 0.3 V (0.13%) | 1.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.14 V (0.06%) | 229.9 V | 0.24 V (0.1%) | 1.4 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.11 V (0.05%) | 229.9 V | 0.19 V (0.08%) | 1.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.09 V (0.04%) | 229.9 V | 0.15 V (0.07%) | 0.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.07 V (0.03%) | 229.9 V | 0.12 V (0.05%) | 0.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.06 V (0.02%) | 229.9 V | 0.09 V (0.04%) | 0.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.04 V (0.02%) | 230.0 V | 0.07 V (0.03%) | 0.4 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 10 Ampere ved 40 Meter (230V)
Hvilket kabeltværsnit kræves til 10A ved 40 meter (230V)?
Til 10 Ampere over 40 meter ved 230V anbefales 2.5 mm² kobberkabel (spændingsfald 6.85V / 2.98%).
Hvor mange kW svarer 10A ved 230V til?
Det svarer til 2.3 kW med en anbefalet sikring på 10A.
Related Lengths & Currents (230V)
10A · 5m (230V)10A · 10m (230V)10A · 15m (230V)10A · 20m (230V)10A · 25m (230V)10A · 30m (230V)10A · 35m (230V)10A · 45m (230V)10A · 50m (230V)10A · 60m (230V)10A · 70m (230V)16A · 40m (230V)20A · 40m (230V)25A · 40m (230V)32A · 40m (230V)40A · 40m (230V)50A · 40m (230V)63A · 40m (230V)80A · 40m (230V)100A · 40m (230V)125A · 40m (230V)160A · 40m (230V)200A · 40m (230V)