Kabeltværsnit for 20 Ampere ved 20 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 20 A over 20 m ved 230V.

Copper Cable (≤3% Drop)2.5 mm²Drop: 6.85V (2.98%)
Aluminum Cable (≤3% Drop)6 mm²Drop: 4.71V (2.05%)
Voltage at Load223.2 VLine Loss: 137.0 W
Max Power & Breaker4.6 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11.41 V (4.96%)218.6 V18.83 V (8.19%)228.3 WDrop High
2.5 mm²24 A18 A6.85 V (2.98%)223.2 V11.3 V (4.91%)137.0 W✓ OK (≤3%)
4 mm²32 A25 A4.28 V (1.86%)225.7 V7.06 V (3.07%)85.6 W✓ OK (≤3%)
6 mm²41 A32 A2.85 V (1.24%)227.1 V4.71 V (2.05%)57.1 W✓ OK (≤3%)
10 mm²57 A44 A1.71 V (0.74%)228.3 V2.82 V (1.23%)34.2 W✓ OK (≤3%)
16 mm²76 A59 A1.07 V (0.47%)228.9 V1.76 V (0.77%)21.4 W✓ OK (≤3%)
25 mm²101 A78 A0.68 V (0.3%)229.3 V1.13 V (0.49%)13.7 W✓ OK (≤3%)
35 mm²125 A97 A0.49 V (0.21%)229.5 V0.81 V (0.35%)9.8 W✓ OK (≤3%)
50 mm²151 A118 A0.34 V (0.15%)229.7 V0.56 V (0.25%)6.8 W✓ OK (≤3%)
70 mm²192 A150 A0.24 V (0.11%)229.8 V0.4 V (0.18%)4.9 W✓ OK (≤3%)
95 mm²232 A181 A0.18 V (0.08%)229.8 V0.3 V (0.13%)3.6 W✓ OK (≤3%)
120 mm²269 A210 A0.14 V (0.06%)229.9 V0.24 V (0.1%)2.9 W✓ OK (≤3%)
150 mm²309 A241 A0.11 V (0.05%)229.9 V0.19 V (0.08%)2.3 W✓ OK (≤3%)
185 mm²353 A275 A0.09 V (0.04%)229.9 V0.15 V (0.07%)1.9 W✓ OK (≤3%)
240 mm²415 A324 A0.07 V (0.03%)229.9 V0.12 V (0.05%)1.4 W✓ OK (≤3%)
300 mm²477 A372 A0.06 V (0.02%)229.9 V0.09 V (0.04%)1.1 W✓ OK (≤3%)
400 mm²570 A445 A0.04 V (0.02%)230.0 V0.07 V (0.03%)0.9 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 20 Ampere ved 20 Meter (230V)

Hvilket kabeltværsnit kræves til 20A ved 20 meter (230V)?

Til 20 Ampere over 20 meter ved 230V anbefales 2.5 mm² kobberkabel (spændingsfald 6.85V / 2.98%).

Hvor mange kW svarer 20A ved 230V til?

Det svarer til 4.6 kW med en anbefalet sikring på 20A.