Kabeltværsnit for 100 Ampere ved 25 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 100 A over 25 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 3.71V (0.93%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 3.06V (0.76%)
Voltage at Load396.3 VLine Loss: 642.0 W
Max Power & Breaker69.28 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A61.78 V (15.44%)338.2 V101.9 V (25.48%)10700.0 WDrop High
2.5 mm²24 A18 A37.07 V (9.27%)362.9 V61.14 V (15.29%)6420.0 WDrop High
4 mm²32 A25 A23.17 V (5.79%)376.8 V38.21 V (9.55%)4012.5 WDrop High
6 mm²41 A32 A15.44 V (3.86%)384.6 V25.48 V (6.37%)2675.0 WDrop High
10 mm²57 A44 A9.27 V (2.32%)390.7 V15.29 V (3.82%)1605.0 WDrop High
16 mm²76 A59 A5.79 V (1.45%)394.2 V9.55 V (2.39%)1003.1 WDrop High
25 mm²101 A78 A3.71 V (0.93%)396.3 V6.11 V (1.53%)642.0 W✓ OK (≤3%)
35 mm²125 A97 A2.65 V (0.66%)397.4 V4.37 V (1.09%)458.6 W✓ OK (≤3%)
50 mm²151 A118 A1.85 V (0.46%)398.1 V3.06 V (0.76%)321.0 W✓ OK (≤3%)
70 mm²192 A150 A1.32 V (0.33%)398.7 V2.18 V (0.55%)229.3 W✓ OK (≤3%)
95 mm²232 A181 A0.98 V (0.24%)399.0 V1.61 V (0.4%)168.9 W✓ OK (≤3%)
120 mm²269 A210 A0.77 V (0.19%)399.2 V1.27 V (0.32%)133.7 W✓ OK (≤3%)
150 mm²309 A241 A0.62 V (0.15%)399.4 V1.02 V (0.25%)107.0 W✓ OK (≤3%)
185 mm²353 A275 A0.5 V (0.13%)399.5 V0.83 V (0.21%)86.8 W✓ OK (≤3%)
240 mm²415 A324 A0.39 V (0.1%)399.6 V0.64 V (0.16%)66.9 W✓ OK (≤3%)
300 mm²477 A372 A0.31 V (0.08%)399.7 V0.51 V (0.13%)53.5 W✓ OK (≤3%)
400 mm²570 A445 A0.23 V (0.06%)399.8 V0.38 V (0.1%)40.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 100 Ampere ved 25 Meter (400V)

Hvilket kabeltværsnit kræves til 100A ved 25 meter (400V)?

Til 100 Ampere over 25 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 3.71V / 0.93%).

Hvor mange kW svarer 100A ved 400V til?

Det svarer til 69.28 kW med en anbefalet sikring på 100A.