⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 40 Ampere ved 25 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 40 A over 25 m ved 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 6.18V (1.54%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 6.11V (1.53%)
Voltage at Load393.8 VLine Loss: 428.0 W
Max Power & Breaker27.71 kW40A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 40A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A24.71 V (6.18%)375.3 V40.76 V (10.19%)1712.0 WDrop High
2.5 mm²24 A18 A14.83 V (3.71%)385.2 V24.46 V (6.11%)1027.2 WDrop High
4 mm²32 A25 A9.27 V (2.32%)390.7 V15.29 V (3.82%)642.0 WDrop High
6 mm²41 A32 A6.18 V (1.54%)393.8 V10.19 V (2.55%)428.0 W✓ OK (≤3%)
10 mm²57 A44 A3.71 V (0.93%)396.3 V6.11 V (1.53%)256.8 W✓ OK (≤3%)
16 mm²76 A59 A2.32 V (0.58%)397.7 V3.82 V (0.96%)160.5 W✓ OK (≤3%)
25 mm²101 A78 A1.48 V (0.37%)398.5 V2.45 V (0.61%)102.7 W✓ OK (≤3%)
35 mm²125 A97 A1.06 V (0.26%)398.9 V1.75 V (0.44%)73.4 W✓ OK (≤3%)
50 mm²151 A118 A0.74 V (0.19%)399.3 V1.22 V (0.31%)51.4 W✓ OK (≤3%)
70 mm²192 A150 A0.53 V (0.13%)399.5 V0.87 V (0.22%)36.7 W✓ OK (≤3%)
95 mm²232 A181 A0.39 V (0.1%)399.6 V0.64 V (0.16%)27.0 W✓ OK (≤3%)
120 mm²269 A210 A0.31 V (0.08%)399.7 V0.51 V (0.13%)21.4 W✓ OK (≤3%)
150 mm²309 A241 A0.25 V (0.06%)399.8 V0.41 V (0.1%)17.1 W✓ OK (≤3%)
185 mm²353 A275 A0.2 V (0.05%)399.8 V0.33 V (0.08%)13.9 W✓ OK (≤3%)
240 mm²415 A324 A0.15 V (0.04%)399.8 V0.25 V (0.06%)10.7 W✓ OK (≤3%)
300 mm²477 A372 A0.12 V (0.03%)399.9 V0.2 V (0.05%)8.6 W✓ OK (≤3%)
400 mm²570 A445 A0.09 V (0.02%)399.9 V0.15 V (0.04%)6.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 40 Ampere ved 25 Meter (400V)

Hvilket kabeltværsnit kræves til 40A ved 25 meter (400V)?

Til 40 Ampere over 25 meter ved 400V anbefales 6 mm² kobberkabel (spændingsfald 6.18V / 1.54%).

Hvor mange kW svarer 40A ved 400V til?

Det svarer til 27.71 kW med en anbefalet sikring på 40A.