Kabeltværsnit for 100 Ampere ved 80 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 100 A over 80 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 9.78V (2.45%)
Voltage at Load388.1 VLine Loss: 2054.4 W
Max Power & Breaker69.28 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A197.68 V (49.42%)202.3 V326.09 V (81.52%)34240.0 WDrop High
2.5 mm²24 A18 A118.61 V (29.65%)281.4 V195.65 V (48.91%)20544.0 WDrop High
4 mm²32 A25 A74.13 V (18.53%)325.9 V122.28 V (30.57%)12840.0 WDrop High
6 mm²41 A32 A49.42 V (12.36%)350.6 V81.52 V (20.38%)8560.0 WDrop High
10 mm²57 A44 A29.65 V (7.41%)370.3 V48.91 V (12.23%)5136.0 WDrop High
16 mm²76 A59 A18.53 V (4.63%)381.5 V30.57 V (7.64%)3210.0 WDrop High
25 mm²101 A78 A11.86 V (2.97%)388.1 V19.57 V (4.89%)2054.4 W✓ OK (≤3%)
35 mm²125 A97 A8.47 V (2.12%)391.5 V13.98 V (3.49%)1467.4 W✓ OK (≤3%)
50 mm²151 A118 A5.93 V (1.48%)394.1 V9.78 V (2.45%)1027.2 W✓ OK (≤3%)
70 mm²192 A150 A4.24 V (1.06%)395.8 V6.99 V (1.75%)733.7 W✓ OK (≤3%)
95 mm²232 A181 A3.12 V (0.78%)396.9 V5.15 V (1.29%)540.6 W✓ OK (≤3%)
120 mm²269 A210 A2.47 V (0.62%)397.5 V4.08 V (1.02%)428.0 W✓ OK (≤3%)
150 mm²309 A241 A1.98 V (0.49%)398.0 V3.26 V (0.82%)342.4 W✓ OK (≤3%)
185 mm²353 A275 A1.6 V (0.4%)398.4 V2.64 V (0.66%)277.6 W✓ OK (≤3%)
240 mm²415 A324 A1.24 V (0.31%)398.8 V2.04 V (0.51%)214.0 W✓ OK (≤3%)
300 mm²477 A372 A0.99 V (0.25%)399.0 V1.63 V (0.41%)171.2 W✓ OK (≤3%)
400 mm²570 A445 A0.74 V (0.19%)399.3 V1.22 V (0.31%)128.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 100 Ampere ved 80 Meter (400V)

Hvilket kabeltværsnit kræves til 100A ved 80 meter (400V)?

Til 100 Ampere over 80 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 11.86V / 2.97%).

Hvor mange kW svarer 100A ved 400V til?

Det svarer til 69.28 kW med en anbefalet sikring på 100A.