Kabeltværsnit for 160 Ampere ved 80 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 160 A over 80 m ved 400V.
Copper Cable (≤3% Drop)70 mm²Drop: 6.78V (1.69%)
Aluminum Cable (≤3% Drop)95 mm²Drop: 8.24V (2.06%)
Voltage at Load393.2 VLine Loss: 1878.3 W
Max Power & Breaker110.85 kW160A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 160A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 316.3 V (79.07%) | 83.7 V | 521.74 V (130.43%) | 87654.4 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 189.78 V (47.44%) | 210.2 V | 313.04 V (78.26%) | 52592.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 118.61 V (29.65%) | 281.4 V | 195.65 V (48.91%) | 32870.4 W | Drop High |
| 6 mm² | 41 A | 32 A | 79.07 V (19.77%) | 320.9 V | 130.43 V (32.61%) | 21913.6 W | Drop High |
| 10 mm² | 57 A | 44 A | 47.44 V (11.86%) | 352.6 V | 78.26 V (19.57%) | 13148.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 29.65 V (7.41%) | 370.3 V | 48.91 V (12.23%) | 8217.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 18.98 V (4.74%) | 381.0 V | 31.3 V (7.83%) | 5259.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 13.56 V (3.39%) | 386.4 V | 22.36 V (5.59%) | 3756.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 9.49 V (2.37%) | 390.5 V | 15.65 V (3.91%) | 2629.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 6.78 V (1.69%) | 393.2 V | 11.18 V (2.8%) | 1878.3 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 4.99 V (1.25%) | 395.0 V | 8.24 V (2.06%) | 1384.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 3.95 V (0.99%) | 396.0 V | 6.52 V (1.63%) | 1095.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 3.16 V (0.79%) | 396.8 V | 5.22 V (1.3%) | 876.5 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.56 V (0.64%) | 397.4 V | 4.23 V (1.06%) | 710.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.98 V (0.49%) | 398.0 V | 3.26 V (0.82%) | 547.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.58 V (0.4%) | 398.4 V | 2.61 V (0.65%) | 438.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 328.7 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 160 Ampere ved 80 Meter (400V)
Hvilket kabeltværsnit kræves til 160A ved 80 meter (400V)?
Til 160 Ampere over 80 meter ved 400V anbefales 70 mm² kobberkabel (spændingsfald 6.78V / 1.69%).
Hvor mange kW svarer 160A ved 400V til?
Det svarer til 110.85 kW med en anbefalet sikring på 160A.
Related Lengths & Currents (400V)
160A · 5m (400V)160A · 10m (400V)160A · 15m (400V)160A · 20m (400V)160A · 25m (400V)160A · 30m (400V)160A · 35m (400V)160A · 40m (400V)160A · 45m (400V)160A · 50m (400V)160A · 60m (400V)160A · 70m (400V)10A · 80m (400V)16A · 80m (400V)20A · 80m (400V)25A · 80m (400V)32A · 80m (400V)40A · 80m (400V)50A · 80m (400V)63A · 80m (400V)80A · 80m (400V)100A · 80m (400V)125A · 80m (400V)200A · 80m (400V)