Kabeltværsnit for 32 Ampere ved 80 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 32 A over 80 m ved 400V.
Copper Cable (≤3% Drop)10 mm²Drop: 9.49V (2.37%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.78V (2.45%)
Voltage at Load390.5 VLine Loss: 525.9 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 63.26 V (15.81%) | 336.7 V | 104.35 V (26.09%) | 3506.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 37.96 V (9.49%) | 362.0 V | 62.61 V (15.65%) | 2103.7 W | Drop High |
| 4 mm² | 32 A | 25 A | 23.72 V (5.93%) | 376.3 V | 39.13 V (9.78%) | 1314.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 15.81 V (3.95%) | 384.2 V | 26.09 V (6.52%) | 876.5 W | ~ ≤5% |
| 10 mm² | 57 A | 44 A | 9.49 V (2.37%) | 390.5 V | 15.65 V (3.91%) | 525.9 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 5.93 V (1.48%) | 394.1 V | 9.78 V (2.45%) | 328.7 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 3.8 V (0.95%) | 396.2 V | 6.26 V (1.57%) | 210.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 2.71 V (0.68%) | 397.3 V | 4.47 V (1.12%) | 150.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 1.9 V (0.47%) | 398.1 V | 3.13 V (0.78%) | 105.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 1.36 V (0.34%) | 398.6 V | 2.24 V (0.56%) | 75.1 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.0 V (0.25%) | 399.0 V | 1.65 V (0.41%) | 55.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.79 V (0.2%) | 399.2 V | 1.3 V (0.33%) | 43.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.63 V (0.16%) | 399.4 V | 1.04 V (0.26%) | 35.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.51 V (0.13%) | 399.5 V | 0.85 V (0.21%) | 28.4 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.4 V (0.1%) | 399.6 V | 0.65 V (0.16%) | 21.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.32 V (0.08%) | 399.7 V | 0.52 V (0.13%) | 17.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.24 V (0.06%) | 399.8 V | 0.39 V (0.1%) | 13.1 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 32 Ampere ved 80 Meter (400V)
Hvilket kabeltværsnit kræves til 32A ved 80 meter (400V)?
Til 32 Ampere over 80 meter ved 400V anbefales 10 mm² kobberkabel (spændingsfald 9.49V / 2.37%).
Hvor mange kW svarer 32A ved 400V til?
Det svarer til 22.17 kW med en anbefalet sikring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 80m (400V)16A · 80m (400V)20A · 80m (400V)25A · 80m (400V)40A · 80m (400V)50A · 80m (400V)63A · 80m (400V)80A · 80m (400V)100A · 80m (400V)125A · 80m (400V)160A · 80m (400V)200A · 80m (400V)