Kabeltværsnit for 110 Ampere ved 10 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 10 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 1.16V (0.29%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 1.35V (0.34%)
Voltage at Load398.8 VLine Loss: 221.9 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A27.18 V (6.8%)372.8 V44.84 V (11.21%)5178.8 WDrop High
2.5 mm²24 A18 A16.31 V (4.08%)383.7 V26.9 V (6.73%)3107.3 WDrop High
4 mm²32 A25 A10.19 V (2.55%)389.8 V16.81 V (4.2%)1942.0 WDrop High
6 mm²41 A32 A6.8 V (1.7%)393.2 V11.21 V (2.8%)1294.7 WDrop High
10 mm²57 A44 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 WDrop High
16 mm²76 A59 A2.55 V (0.64%)397.5 V4.2 V (1.05%)485.5 WDrop High
25 mm²101 A78 A1.63 V (0.41%)398.4 V2.69 V (0.67%)310.7 WDrop High
35 mm²125 A97 A1.16 V (0.29%)398.8 V1.92 V (0.48%)221.9 W✓ OK (≤3%)
50 mm²151 A118 A0.82 V (0.2%)399.2 V1.35 V (0.34%)155.4 W✓ OK (≤3%)
70 mm²192 A150 A0.58 V (0.15%)399.4 V0.96 V (0.24%)111.0 W✓ OK (≤3%)
95 mm²232 A181 A0.43 V (0.11%)399.6 V0.71 V (0.18%)81.8 W✓ OK (≤3%)
120 mm²269 A210 A0.34 V (0.08%)399.7 V0.56 V (0.14%)64.7 W✓ OK (≤3%)
150 mm²309 A241 A0.27 V (0.07%)399.7 V0.45 V (0.11%)51.8 W✓ OK (≤3%)
185 mm²353 A275 A0.22 V (0.06%)399.8 V0.36 V (0.09%)42.0 W✓ OK (≤3%)
240 mm²415 A324 A0.17 V (0.04%)399.8 V0.28 V (0.07%)32.4 W✓ OK (≤3%)
300 mm²477 A372 A0.14 V (0.03%)399.9 V0.22 V (0.06%)25.9 W✓ OK (≤3%)
400 mm²570 A445 A0.1 V (0.03%)399.9 V0.17 V (0.04%)19.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 10 Meter (400V)

Hvilket kabeltværsnit kræves til 110A ved 10 meter (400V)?

Til 110 Ampere over 10 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 1.16V / 0.29%).

Hvor mange kW svarer 110A ved 400V til?

Det svarer til 76.21 kW med en anbefalet sikring på 110A.