Kabeltværsnit for 110 Ampere ved 50 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 50 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 5.82V (1.46%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 6.73V (1.68%)
Voltage at Load394.2 VLine Loss: 1109.7 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A135.91 V (33.98%)264.1 V224.19 V (56.05%)25894.0 WDrop High
2.5 mm²24 A18 A81.54 V (20.39%)318.5 V134.51 V (33.63%)15536.4 WDrop High
4 mm²32 A25 A50.97 V (12.74%)349.0 V84.07 V (21.02%)9710.2 WDrop High
6 mm²41 A32 A33.98 V (8.49%)366.0 V56.05 V (14.01%)6473.5 WDrop High
10 mm²57 A44 A20.39 V (5.1%)379.6 V33.63 V (8.41%)3884.1 WDrop High
16 mm²76 A59 A12.74 V (3.19%)387.3 V21.02 V (5.25%)2427.6 WDrop High
25 mm²101 A78 A8.15 V (2.04%)391.8 V13.45 V (3.36%)1553.6 WDrop High
35 mm²125 A97 A5.82 V (1.46%)394.2 V9.61 V (2.4%)1109.7 W✓ OK (≤3%)
50 mm²151 A118 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 W✓ OK (≤3%)
70 mm²192 A150 A2.91 V (0.73%)397.1 V4.8 V (1.2%)554.9 W✓ OK (≤3%)
95 mm²232 A181 A2.15 V (0.54%)397.9 V3.54 V (0.88%)408.9 W✓ OK (≤3%)
120 mm²269 A210 A1.7 V (0.42%)398.3 V2.8 V (0.7%)323.7 W✓ OK (≤3%)
150 mm²309 A241 A1.36 V (0.34%)398.6 V2.24 V (0.56%)258.9 W✓ OK (≤3%)
185 mm²353 A275 A1.1 V (0.28%)398.9 V1.82 V (0.45%)210.0 W✓ OK (≤3%)
240 mm²415 A324 A0.85 V (0.21%)399.2 V1.4 V (0.35%)161.8 W✓ OK (≤3%)
300 mm²477 A372 A0.68 V (0.17%)399.3 V1.12 V (0.28%)129.5 W✓ OK (≤3%)
400 mm²570 A445 A0.51 V (0.13%)399.5 V0.84 V (0.21%)97.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 50 Meter (400V)

Hvilket kabeltværsnit kræves til 110A ved 50 meter (400V)?

Til 110 Ampere over 50 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 5.82V / 1.46%).

Hvor mange kW svarer 110A ved 400V til?

Det svarer til 76.21 kW med en anbefalet sikring på 110A.