Kabeltværsnit for 110 Ampere ved 5 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 5 m ved 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 0.58V (0.15%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.67V (0.17%)
Voltage at Load399.4 VLine Loss: 111.0 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A13.59 V (3.4%)386.4 V22.42 V (5.6%)2589.4 WDrop High
2.5 mm²24 A18 A8.15 V (2.04%)391.8 V13.45 V (3.36%)1553.6 WDrop High
4 mm²32 A25 A5.1 V (1.27%)394.9 V8.41 V (2.1%)971.0 WDrop High
6 mm²41 A32 A3.4 V (0.85%)396.6 V5.6 V (1.4%)647.4 WDrop High
10 mm²57 A44 A2.04 V (0.51%)398.0 V3.36 V (0.84%)388.4 WDrop High
16 mm²76 A59 A1.27 V (0.32%)398.7 V2.1 V (0.53%)242.8 WDrop High
25 mm²101 A78 A0.82 V (0.2%)399.2 V1.35 V (0.34%)155.4 WDrop High
35 mm²125 A97 A0.58 V (0.15%)399.4 V0.96 V (0.24%)111.0 W✓ OK (≤3%)
50 mm²151 A118 A0.41 V (0.1%)399.6 V0.67 V (0.17%)77.7 W✓ OK (≤3%)
70 mm²192 A150 A0.29 V (0.07%)399.7 V0.48 V (0.12%)55.5 W✓ OK (≤3%)
95 mm²232 A181 A0.21 V (0.05%)399.8 V0.35 V (0.09%)40.9 W✓ OK (≤3%)
120 mm²269 A210 A0.17 V (0.04%)399.8 V0.28 V (0.07%)32.4 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.03%)399.9 V0.22 V (0.06%)25.9 W✓ OK (≤3%)
185 mm²353 A275 A0.11 V (0.03%)399.9 V0.18 V (0.05%)21.0 W✓ OK (≤3%)
240 mm²415 A324 A0.08 V (0.02%)399.9 V0.14 V (0.04%)16.2 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.02%)399.9 V0.11 V (0.03%)12.9 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.01%)399.9 V0.08 V (0.02%)9.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 5 Meter (400V)

Hvilket kabeltværsnit kræves til 110A ved 5 meter (400V)?

Til 110 Ampere over 5 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 0.58V / 0.15%).

Hvor mange kW svarer 110A ved 400V til?

Det svarer til 76.21 kW med en anbefalet sikring på 110A.