⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 110 Ampere ved 350 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 350 m ved 400V.

Copper Cable (≤3% Drop)120 mm²Drop: 11.89V (2.97%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 9.81V (2.45%)
Voltage at Load388.1 VLine Loss: 2265.7 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A951.36 V (237.84%)0.0 V1569.3 V (392.32%)181258.0 WDrop High
2.5 mm²24 A18 A570.81 V (142.7%)0.0 V941.58 V (235.39%)108754.8 WDrop High
4 mm²32 A25 A356.76 V (89.19%)43.2 V588.49 V (147.12%)67971.8 WDrop High
6 mm²41 A32 A237.84 V (59.46%)162.2 V392.32 V (98.08%)45314.5 WDrop High
10 mm²57 A44 A142.7 V (35.68%)257.3 V235.39 V (58.85%)27188.7 WDrop High
16 mm²76 A59 A89.19 V (22.3%)310.8 V147.12 V (36.78%)16992.9 WDrop High
25 mm²101 A78 A57.08 V (14.27%)342.9 V94.16 V (23.54%)10875.5 WDrop High
35 mm²125 A97 A40.77 V (10.19%)359.2 V67.26 V (16.81%)7768.2 WDrop High
50 mm²151 A118 A28.54 V (7.14%)371.5 V47.08 V (11.77%)5437.7 WDrop High
70 mm²192 A150 A20.39 V (5.1%)379.6 V33.63 V (8.41%)3884.1 WDrop High
95 mm²232 A181 A15.02 V (3.76%)385.0 V24.78 V (6.19%)2862.0 W~ ≤5%
120 mm²269 A210 A11.89 V (2.97%)388.1 V19.62 V (4.9%)2265.7 W✓ OK (≤3%)
150 mm²309 A241 A9.51 V (2.38%)390.5 V15.69 V (3.92%)1812.6 W✓ OK (≤3%)
185 mm²353 A275 A7.71 V (1.93%)392.3 V12.72 V (3.18%)1469.7 W✓ OK (≤3%)
240 mm²415 A324 A5.95 V (1.49%)394.1 V9.81 V (2.45%)1132.9 W✓ OK (≤3%)
300 mm²477 A372 A4.76 V (1.19%)395.2 V7.85 V (1.96%)906.3 W✓ OK (≤3%)
400 mm²570 A445 A3.57 V (0.89%)396.4 V5.88 V (1.47%)679.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 110 Ampere ved 350 Meter (400V)

Hvilket kabeltværsnit kræves til 110A ved 350 meter (400V)?

Til 110 Ampere over 350 meter ved 400V anbefales 120 mm² kobberkabel (spændingsfald 11.89V / 2.97%).

Hvor mange kW svarer 110A ved 400V til?

Det svarer til 76.21 kW med en anbefalet sikring på 110A.